Installation And Electrical Connection; Pump Installation - Wilo Stratos Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7 Installation and electrical connection

Installation and electrical work in compliance with any local codes and by
qualified personnel only!
WARNING! Bodily injury
Existing regulations for the prevention of accidents must be observed.
WARNING! Electrical shock hazard
Dangers caused by electrical energy must be excluded.
National Electrical Codes, local codes and regulations must be followed.

7.1 Pump installation

• The pump must be installed in a dry, well-ventilated and frost-free place.
CAUTION! Possible damage of the pump
Dirt and solder drops in the pump body can effect the pump operation.
• It is recommended that any welding and soldering work be done before
installing the pump.
• Thoroughly flush the system prior to installing and operating the pump.
• Foreign material in the system resulting from construction may damage the
pump and is not warrantable.
• The pump must be installed in an easily accessible position to facilitate
inspection or replacement.
• The pump should never be located at the lowest point of the piping system,
where dirt and sediment collect. Nor should it be located at the highest point of
the piping system, where air accumulates. Please ensure at least a minimum of
three pipe diameters of straight on the suction side of the pump.
• It is recommended that isolation valves be installed on the suction and
discharge side of the pump.
This will save having to drain and refill the system if the pump / pump head
needs exchange-service. The valves are to be installed so that any water that
escape cannot drip onto the pump motor or terminal box.
• An arrow on the pump housing indicates the direction of water flow (fig.1, pos.2).
• Install the pump in an easily accessible place, so that subsequent servicing work
can easily be carried out.
Installation is to be carried out such that dripping water cannot drip onto the
pump motor or control module.
• Pump must be installed with the shaft in the horizontal position in such a way
that it is not stressed by the pipework. (Installation positions in fig. 2). When
installing in confined spaces, for example in compact distributors, the control
module can be placed in a vertical position by rotating the motor, see
chapter 7.1.1.
Installation and operating instructions Wilo-Stratos