Technical Data; Plug And Socket Ghg 515 - Eaton CROUSE-HINDS Série Mode D'emploi

Fiche et prise de 125 a, à 4 pôles et 5 pôles, pour atmosphères explosives
Masquer les pouces Voir aussi pour CROUSE-HINDS Série:
Table des Matières

Publicité

Code Zone 1
3-pole + PE
3-pole +N + PE
GHG 515, 3-pole + PE
50/60Hz
220-250V
380-415V
500V
blue
red
black
GHG 515, 4-pole + PE
50/60Hz
220-250V
380-415V
500V
blue
red
black
Dimensions in mm
X = fixing dimensions
Plug
Wall socket
Explosion-protected plugs and sockets 125 A, GHG 515
1

Technical data

1.1

Plug and socket GHG 515

Marking acc. to 2014/34/EU:
EC type examination certificate:
Rated voltage:
Rated current:
Back-up fuse:
Switching capacity AC 3:
Perm. ambient temperature:
(Other temperatures possible for special versions.)
Perm. storage temperature in original packing:
**Protection category acc. to IEC/EN 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to IEC/EN 61140:
Cable entry:
Wall socket
690V
suitable cables and test torques of the
black
pressure screw
Seal 1+2+3
1 2
Seal 1+2
1 2
Seal 1
1 2
Test torque for screw in thread cable entry
(1) The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use the
690V
combination of sealing 1 + 2 + 3 for the intermediate region.
black
(2) When selecting the seal rubber, ensure that the pressure screw can be tightened when carrying out any
future maintenance work on the cable entry.
Plug
Terminal
Wall socket:
Plug:
* (use cable lugs supplied) Observe current load!)
Min. cross section / Supply terminal
for 100 A rated current
for 125 A rated current
Test torques
Cover screws:
Terminals, plug:
Terminals, wall socket:
Self-cutting screws size 5:
Weight (standard version)
Wall socket:
Plug:
Auxiliary contact
Rated voltage:
Rated current:
Switching capacity:
D II 2 G Ex de IIC T6
D II 2 D Ex tD A21 IP66 T 80°C
PTB 01 ATEX 1069
up to 690 V, 50/60 Hz
max. 125 A
max. 125 A gL without thermal protection
max. 160 A gL with thermal protection (therm.
protection set to 125 A)
up to 690 V / 125 A
-20 °C to +40 °C (standard version)
-20 °C to +40 °C
IP 66 (catalogue version)
II - is complied with by devices
(standard version)
2 x M63
Ø
min.
--
3
max. (1)(2)
min.
29.0
3
max. (1)(2)
35.0
min.
36.0
3
max. (2)
41.0
7 .5 Nm
Ø 21-48 mm (Ø 31-58 mm)
2 x 4 - 70 mm² (max 1x120 mm²)*
1 x 4 - 35 mm² with pin cable lugs 1x50 mm²
Wall socket
1x 50 mm²
1x 70 mm²
2.5 Nm
4.5 Nm
6.0 Nm
3.0 Nm (see page 10, fig. 3, pos5)
4-pole
approx. 12.30 kg
approx.
690 V AC
20 A
AC 15
DC 13
4-pole
5-pole
w/o auxiliary contact
Nm
--
12.0
12.0
12.0
13.0
Plug
1x 35 mm²
1x 50 mm²
5-pole
approx. 13.00 kg
0.90 kg
approx.
1.20 kg
400 V / 6 A
24 V / 2 A
Contact arrangement
with auxiliary contact
GB
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Crouse-hinds ghg 515

Table des Matières