Cleaning and caring for the inverter

9
Cleaning and caring for the inverter
Caution
a
Do not use any sharp or hard objects for cleaning since they may
damage the device.
➤ Occasionally clean the device with a damp cloth.
10

Rectifying faults

Note
I
If you have detailed questions on the specifications of the
inverter please contact WAECO.
Fault
No output voltage
Warning signal during
operation
Warning sound during
operation below nominal
load
The device switches on and
off repeatedly
The inverter switches off
when the consumer is
switched on
30
Cause
No contact to the battery
Battery voltage less than 11 V
(MSP 162/MSP 352) or 22 V
(MSP 164/MSP 354)
Overheating
Defective fuse (in the inverter
or the vehicle)
The battery voltage is less than
11 V (MSP 162/MSP 352) or
22 V (MSP 164/MSP 354)
Poor contact to the battery
Insufficient battery power.
Inadequate cable connection
(cross section too small or poor
contact).
Excessive constant load
Starting current too high
SinePower
Remedy
Check contact and cable.
Charge the battery (start the
engine).
Switch off power consuming
devices.
Let the inverter cool down
and ensure better ventilation.
Have an electrician change
the fuse.
Charge the battery.
Clean the contacts.
Charge the battery.
Use a cable with a larger
cross section and check
contacts.
Reduce the load.
Compare the device power
with the maximum power of
the inverter.