Installation and Operating Instructions
EN
Compact Ventilation Units AIR1 XC
33.25 W power is available for connecting the air quality sensors. However, this power is reduced depending on the
additional accessories connected.1
For the connection of the sensors, the available 24 V supply on the basis of the table must therefore be observed.
The DC power available for 24 V accessory components is 33.25 W.
Accessory components (AIR1 XC Units)
AIR1-BE TOUCH

Controller connection

AIR1-BE ECO
Controller connection
AIR1-ENH
Electrical after heater
AIR1-NH WW
Water heater (Mixing valve)
Cold water cooling (valve)
AIR1-KR KW
AIR1-JVK
Volume control dampers (2 x)
AIR1-ULK
Recirculation damper (RH 5000)
AIR1/KWL-CO2 0-10V
CO2-sensor
AIR1/KWL-FTF 0-10V
Humidity / temperature sensor
AIR1/KWL-VOC 0-10V
Mixed gas sensor
AIR1-CO2 K
CO2-channel sensor
Duct smoke sensor
RMK
11
Power required
6 W
0,24 W
6 W
6 W
6 W
5 W (2 x 2,5 W)
1 W
0,6 W
0,6 W
0,6 W
2 W
0,6 W