Helios AIR1 XC 500 L Notice De Montage Et D'entretien page 106

Table des Matières

Publicité

Installation and Operating Instructions
EN
The submenus of the main menu (Part 2 of 2)
7. Inputs / Outputs
AI
AI exp3
AI exp4
DI
UI
Each with arrow to the right
UI exp 3
to view signals at
UI exp 4
inputs / outputs.
AO
Each with arrow to the right
DO
to view signals at
inputs / outputs.
8. Manual / Auto
Supply temp contr
Auto
Manual setting: 100.0
SAF: Auto
Manual set: 100.0
EAF: Auto
Manual set: 100.0
Exchanger
Auto
Manual set: 100.0
P1 heating
Auto
P1 exchanger
Auto
P1 cooling
Auto
Outdoor air damper
Auto
Exhaust air damper
Auto
Extra sequence Y5
Auto
Manual set: 0.0
Compact Ventilation Units AIR1 XC
9. Settings
AI1: 0.0 Inactive
Control temp
AI2: 45.5 Humidity
Control flow
AI3: 0.0 Inactive
Alarm settings
AI4: 0.0 Inactive
Restore factory
settings: No
Restore user
settings: No
Save user settings:
No
10. Configuration
Inputs / Outputs
Use the arrow to the right
Sensor settings
to go to the submenus.
Control function
Display on the
Fan control
following pages
Extra sequenc e Y4
Use the arrow to the right
Extra sequence Y5
to go to the submenus.
Heating
Display on the
Exchanger
following pages
Cooling
Use the arrow to the right
Pump control
to go to the submenus.
Free cooling
Display on the
Support control
following pages
Fire function
Use the arrow to the right
Smoke detector func
to go to the submenus.
Exchanger deicing
Display on the
Exch frost prevent
following pages
Cooling recovery
Use the arrow to the right
Min limit dampers
to go to the submenus.
Run ind/Motor prot
Display on the
Type of actuator
following pages
Actuator run time
Use the arrow to the right
Actuator period tim
to go to the submenus.
Step controllers
Display on the
Recirculation
following pages
Alarm settings
Use the arrow to the right
Communication
to go to the submenus.
Other parameters
Display on the
System
following pages
Supply air control
P-band: 33.0 °C
I-time: 100.0 s
Frost protection
Flow control SAF
P-band: 21250.0 m3/h
I-time:
60.0 s
Min. output: 0
%
Flow control EAF
P-band: 21250.0 m3/h
I-time:
60.0 s
Min. output: 0
%
Alarm limits
Alarm delays
Restore alarm
Service alarm
(Filter alarm)
Time counter set
to zero: No
43
Frost protection
Active
Setp shutdown: 25.0C
P-band active: 5.0C
Fast stop at frost-
protection alarm: Yes
Sequence with
frost prot
Y1 heating
Al lim supply air
Control dev : 10.0 °C
High temp : 35.0 °C
Low temp: 10.0 °C
Al del supply air
Al lim extract air
Control dev : 30 Min
High temp : 30.0 °C
High temp : 5 s
Low temp : 10.0 °C
Low temp : 5 s
Al del extract air
Control dev
high temp : 30 min
SAF: 50.0 m3/h
Low temp : 30 min
Alarm delay
Control dev
Frost prot: 0 s
EAF: 50.0 m3/h
Frost risk : 0 s
Alarm delay control
Low efficiency
dev pressure
50.0 %
SAF: 30 Min
Service alarm
Alarm delay control
(Filter alarm)
dev pressure
Time until alarm
EAF: 30 Min
activates: 0 months
Alarm limit (X1, Y1)
Low efficiency
filter guard1
30 min
22.0
Pa at
0
m3/h
Alarm limit (X2, Y2)
Alarm delay
filter guard1
malfunction
90
Pa at
SAF: 120 s
4500
m3/h
Alarm limit (X3, Y3)
Alarm delay
filter guard1
malfunction
178.8
EAF: 120 s
10000
Alarm delay malfunc
Alarm limit (X1, Y1)
P1 heating: 5 s
filter guard2
P1 cooling : 5 s
20.0
P1 exchan : 20 s
0
Alarm limit (X2, Y2)
Filter guard1: 180s
filter guard2
Filter guard2: 180s
75
Flow switch : 5 s
Frost prot: 0 s
4500
Alarm delay
Alarm limit (X3, Y3)
Deicing DI: 0 s
filter guard2
Fire alarm : 0 s
165.8
Ext alarm
: 0 s
10000 m3/h
Alarm delay
Elec heat
: 0 s
Sensor error : 15 s
Rot sent exch: 20 s
Pa at
m3/h
Pa at
m3/h
Pa at
m3/h
Pa at

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Air1 xc 700 lAir1 xc 1400 lAir1 xc 500 rAir1 xc 700 rAir1 xc 1400 rAir1 xc 2200 l ... Afficher tout

Table des Matières