Installation and Operating Instructions
EN
ATTENTION
ATTENTION
Compact Ventilation Units AIR1 XC
Stop conditions:
– The outside temperature is higher than the set start value (e.g. 18 °C) or lower than the set minimum value (e.g. 10
°C).
– The room temperature is lower than the set stop value (e.g. 18 °C).
– A ventilation stage other than those listed above is active.
– It is not the set time of day.
The start and stop conditions must be set in the commissioning assistant.
Free cooling / Free heating
This function opens the bypass under the conditions described below. This uses the intake air temperature for heating
or cooling.
1. If the unit has heating requirements:
Case 1 – If the supply air temperature < intake air temperature and the extract air temperature < intake air temperature,
then the bypass shutter is opened.
Case 2 – If the supply air temperature < intake air temperature and the extract air temperature > intake air temperature,
then the bypass shutter is closed.
2. If the unit has cooling requirements:
Case 3 – If the supply air temperature > intake air temperature and the extract air temperature > intake air temperature,
then the bypass shutter is opened.
Case 4 – If the supply air temperature > intake air temperature and the extract air temperature < intake air temperature,
then the bypass shutter is closed.
Prevention of pressure losses
If the supply air, extract air, intake air and exhaust air temperatures are equal, heat recovery is not required. The unit
opens the bypass shutter to prevent unnecessary pressure loss.
If the supply air temperature = intake air temperature = extract air temperature = exhaust air temperature, then the
bypass shutter is opened.
4�1�6 Overrun
The unit has an adjustable overrun function for ventilation stage selection via an external switch contact.
Thus, the ventilation unit will run for the set time after actuation of the switch contact for the respective ventilation stage.
Therefore, a push-button function is possible.
If the overrun time is set to 0,the ventilation unit will run until the corresponding switch contact is no longer actuated.
Adjustment of overrun time:
• Log on as User or Administrator
• Call up the "Timer" menu
• Call up the "Overrun" menu
• Set the desired overrun time

Overrun

XXX min
Time in overrun
XXX min

4.1.7 Additional operating settings

The following additional settings can be adjusted and the following information can be seen in the main menu for the
controller AIR1-BE Eco (Controller AIR1-BE Touch see separate manual):
Selected functions
"Extended overview" - Overview page with system information
Inputs/outputs
Signals to all control inputs/outputs can be checked (not adjustable)
Manual/Auto (function test)
Individual functions, such as a fan or damper, can be manually controlled (see section Manual/Auto (function test) in the
service section of these installation and operating instructions).

Configuration

"Configuration" - Same function as the commissioning assistant with extended scope and no sequenced query (see
Commissioning assistant section in the Commissioning section).
Settings other than those specified in this manual are not recommended!
Settings
"Professional settings" - Extensive modifications to the controller can be carried out in the settings, e.g. alarm changes.
This function may only be used by specialist personnel.
Settings other than those specified in this manual are not recommended.
OK
OK
OK
OK