Relay Menu

The Relay menu allows users to select Latch, Failsafe, or SetDelay.
Press enter to access the Relay menu options, then scroll to select
Relay #1 or Relay #2.
Use the arrow keys to scroll to the desired option and press enter to
select one of the four following options:
Latch:
Keeps relays on even after an event has returned to normal.
Use the arrow keys to select Yes or No and press enter to
confirm the setting. Once a latched relay is activated, press
and hold a keypad button for 5 seconds to return relays to
their normal position.
Failsafe:
Relays will be on in normal conditions but will de-energize
during a controller fault or shutdown, or when an alarm is
triggered. In the Failsafe menu, use the arrow keys to select
either Yes or No and press enter to confirm.
Activate:
Relay #2 only. Can be set to activate with B (Alarm B) or F
(Fault).
SetDelay:
Allows users to specify a Before and After delay period for
relay alarm activation and deactivation.
In the SetDelay menu, use the arrow keys to display either
Before or After and press enter to select.
For the Before (or After) screen, use the arrow keys to increase
the delay in seconds. When the desired value is reached, press
enter to confirm.
Press enter again to confirm the SetDelay, or use the arrow
keys to select No and cancel the procedure.
E
Point Standalone Gas Monitor User Manual
3
* Menu *
Relay
Relay #1
Latch
SetDelay
Before
Before
000 sec
SetDelay
Yes
Using the Programming Menus
Relay
Relay #1
17

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

E3point

Table des Matières