Central ventilation unit – KWL 470 W/W ET
4.3
Install ball siphon
During heating periods, condensate may form in the heat exchanger due to the heat recovery process. The condensa-
te must be able to drain freely from the unit. The provided ball siphon (scope of delivery) must be installed in the base
tray of the unit for this purpose.
1. Open ball siphon. Turn the mounting part a 1/4 turn (see Fig. 11).
2. Plug the mounting part in the condensate outlet from below, until the claw fasteners snap to the sheet edge of the
base plate (Fig. 12).
3. Insert locking part and insert up to stop (Fig. 13).
4. Then insert the condensate hose (DN 12 mm; not included in delivery) in the hose connector on the siphon casing
and tighten by hand (Fig. 14).
5. Connect siphon casing and turn a 1/4 turn in the mounting part (see Fig. 15). Ensure that the float ball is loose in
the casing!
Water damage in the unit due to condensation.
A closed discharge can lead to pressure conditions which prevent controlled drainage from the unit. Furthermo-
re, gases may escape from the drainage line into the unit, which may create a breeding ground for microorga-
nisms in combination with moisture.
> The condensate hose must end 20 mm above the open drain or possible water level (see Fig. 16).
> The condensate hose from the ball siphon must have a downward gradient, openly dripping into a funnel
siphon and must not be discharged into a closed system (see Fig. 16).
Connect siphon
casing
Fig. 11
View below
Fig. 13
Fig. 15
1/4 turn
12
View above
ø12, hose
ø12, Schlauch
max. 1.5 m long
max.1,5m lang,
Note gradient
Funnel
Trichter-
Gefälle beachten
siphon
siphon
EN
Fig. 12
Fig. 14
Fig. 16