8. TECHNICAL SPECIFICATIONS 5kVA, 8kVA, 10kVA:
MultiPlus-II
PowerControl / PowerAssist
AC input
Maximum feed through current
Input voltage range
Output
(1)
Cont. output power at 25 °C / 77
°F
Cont. output power at 25 °C / 77
°F
Cont. output power at 40 °C / 104
°F
Cont. output power at 65 °C / 150
°F
Maximum feed-in power
Peak power
Maximum efficiency
Zero-load power
Zero-load power in AES mode
Zero-load power in Search mode
AC input
Charge voltage 'absorption'
Charge voltage 'float'
Storage mode
Charge current house battery
(4)
Auxiliary output
External AC current sensor
(optional)
Programmable relay
(5)
Protection
(2)
VE.Bus communication port
General purpose com. port
Common Characteristics
Material & Colour
Battery-connection
230 VAC-connections
Weight
Dimensions (hxwxd) mm
Safety
Emission / Immunity
Uninterruptible power supply
Anti-islanding
1) Can be adjusted to 60 Hz; 120V 60 Hz on request
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230 VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for general
alarm, DC undervoltage or genset start/stop function
AC rating: 230V / 4A
DC rating: 4A up to 35VDC and 1A upto 60VDC
20
24/5000/120-50
Input voltage range: 187-265 VAC
50 A
9.5 – 17 V
19 – 33 V
Output voltage: 230 VAC ± 2 %
5000 VA
4000 W
3700 W
3000 W
5000 VA
9000 W
95 %
20 W
15 W
3 W
Input voltage range: 187-265 VAC
120 A
Yes (32 A)
Default setting: switches off when in inverter
mode
For parallel and three phase operation, remote monitoring and system integration
Operating temp.: -40 to +65 °C (-40 – 150 °F) (fan assisted cooling)
Steel, blue RAL 5012
M8 bolts
Screw terminals 13 mm² (6 AWG)
30 kg
607 x 330 x 149
EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3
48/5000/70-50
48/8000/110-100/100
Yes
Input frequency: 45 – 65 Hz
50 A
INVERTER
38 – 66 V
96 %
18 W
12 W
2 W
CHARGER
Input frequency: 45 – 65 Hz
14.4 / 28.8 / 57.6 V
13.8 / 27.6 / 55.2 V
13.2 / 26.4 / 52.8 V
70 A
GENERAL
Yes (50 A)
100 A
Yes
a - g
Yes, 2x
Humidity (non-condensing): max 95 %
ENCLOSURE
Protection category: IP22
30 kg
565 x 320 x 149
STANDARDS
EN 60335-1, EN 60335-2-29, IEC62109-1, IEC62109-2
IEC 61000-6-1, EN 61000-6-2, EN 61000-6-3
Please consult the certificates on our website.
Please consult the certificates on our website.
48/10000/140-100/100
100 A
38 – 66 V
Frequency
50 Hz ± 0,1 %
:
8000 VA
6400 W
5500 W
4000 W
8000 VA
15000 W
95 %
29 W
19 W
3 W
Power factor: 1
110
Default setting: switches off when in inverter
mode
Pollution degree 2, OVC3
Four M8 bolts (2 plus and 2 minus connections)
Bolts M6
41.2 kg
642 x 363 x 206
100 A
38 – 66 V
10000 VA
8000 W
7000 W
6000 W
10000 VA
18000 W
96 %
38 W
27 W
4 W
140
Bolts M6
48.8 kg
677 x 363 x 206

Publicité