Warnings
Plain text message
FILTER WECHSELN (change filter)
The differential pressure switches switch
via the air filters when the max.
permissible pressure drop is exceeded.
HEIZUNG ZU KALT (heating too cold)
After 30 min under full load the RHZ
temperature must reach a value of at
least 60 °C, in controlled operation the
value is not prompted.
WENIG REGEN.-LUFT (little amount of
regeneration air)
Differential pressure switch monitors the
pressure loss via regeneration heating
and regeneration sector at the rotor and
releases the heating when a minimum
value is reached.
Faults
Plain text message
VENTI. PROZ.LUFT (fan process air)
Fault message from EC motor
VENTI. REGEN.LUFT (fan regeneration
air)
Fault message from EC motor
ROTOR-ANTRIEB (rotor drive)
Rotor rotation control/inductive proximity
switch is evaluated
THERMOSTATE (thermostats)
Safety temperature limiters (STB) are
prompted.
If an additional heating is used, the STB
is prompted, too.
If the fault cannot be rectified, please contact one of our
subsidiaries or our headquarters.
EN
Cause of error
• filter dirty
• regeneration air not reaching the
minimum temperature
• regeneration air volume too high
• intake temperature too low
• control signals interrupted
• regeneration air volume too low
• regeneration air filter dirty
• pressure loss at piping or on-site
components too high
• regeneration air fan defective or
phases faulty
• incorrect flow direction
• negative pressure at regeneration air
inlet to high
Cause of error
• fan reports a fault
• fan defective
• differential pressure transmitter
defective
• phase error/mains supply AC/DC
• fan reports a fault
• phase error/mains supply AC/DC
• fan defective
• toothed belt slipping
• toothed washer loosened
• gear motor defective
• fuse tripped
• At least one STB tripped.
desiccant dehumidifier TTR 800 / TTR 1400
Measure
• Replace all air filters.
• Check heater current, if required,
repair heater battery.
• Check regeneration air volume.
• Check switching devices and contacts.
• Adjust the regeneration air volume.
• Replace air filter.
• Check piping.
• Check rotary field.
• Replace fan.
Measure
• Check fan, have it replaced if
necessary.
• Check wiring and contacts.
• Check mains supply.
• Adjust air volume.
• Check fan, have it replaced if
necessary.
• Check wiring and contacts.
• Check mains supply.
• Check belt tension and carrier.
• Tighten toothed washer or have it
replaced.
• Check gear motor, have it replaced if
necessary.
• Check voltage supply and signal line of
gear motor.
• Check STBs for proper functioning,
clean sensors if necessary.
• Selected max. RHZ is too high.
• Check setting at STB, adjust.
• Check regeneration air volume.
28