All optional displays only appear if the respective
function was activated at the factory.
Basic settings
The basic settings are made in the factory. Signal conversions
and the corresponding scales must be coordinated with Trotec
prior to delivery or can be adjusted (optionally) during start-up
by Trotec service personnel.
For applications with moisture control it is recommended to
request the Trotec service personnel for possibly required fine
adjustments of the control parameters.
Changing values
ü Values that can be modified are highlighted by flashing bars
(black bar in the example below).
1. Within the screen you can move up and down using the
buttons + and -.
2. In order to edit the value, press the OK button.
ð The flashing bar disappears and the value is displayed.
3. Press the buttons + or - to increase or reduce the value.
4. Confirm your selection by pressing the OK button.
Abort unwanted changes using ESC.
5. Press the buttons + or - to go to the next changeable
value.
6. Repeat the steps 2 to 4 until all values are set.
EN
Emergency operation
If the Millenium logic module fails, the following changes have
to be made:
• Setting the regeneration air heating to emergency
operation
Warning of electrical voltage
Work on the electrical components must only be
carried out by a qualified electrician!
Please proceed as follows to set the regeneration air heating to
emergency operation:
1. Find the terminals 5, 23 and 39 to 41 on the terminal
strip X6.
2. Set the first jumper from X6.23 to X6.41 as shown below.
desiccant dehumidifier TTR 800 / TTR 1400
26