Télécharger Imprimer la page

Trotec TTR 1400 Traduction De La Notice Originale page 77

Déshydrateur à adsorption

Publicité

Les langues disponibles

Les langues disponibles

3. Set the second jumper from X6.5 to X6.39 as shown
below.
4. In the second line from the bottom, disconnect the three
wires of the contacts X6.39, X6.40, X6.41 as shown below.
5. Isolate each of the three disconnected wires using a luster
terminal or similar.
6. Set a jumper from X6.40 to X6.41. The modifications are
completed.
27
Warnings and faults
Note
Rectify any faults immediately to ensure economical
operation of the device.
• During operation the electrical components relevant for the
respective operating mode are monitored for proper
functioning.
• In case of failure or malfunctions plain text messages are
indicated on the display of the logic module so as to enable
quick troubleshooting.
• Depending on the level of impairment of the device's
operational safety the messages are divided into warnings
and faults.
• A warning does not entail the shutdown of the device and
is displayed by periodically recurring plain text messages
on the display. The "warning" indicator light lights up.
• In case of faults the device is shut down (STOP) and the
indicator light "fault" lights up.
• For reasons of safety the device can only be restarted after
the faults have been rectified and the RESET button has
been actuated ( => deletes the error memory).
• The source of a fault will be permanently indicated on the
display. Until the fault is rectified, it will be displayed again
before long whilst the action linked to the fault is triggered.
Error and fault messages can be reset by pressing the reset
button.
desiccant dehumidifier TTR 800 / TTR 1400
EN

Publicité

loading

Ce manuel est également adapté pour:

Ttr 800