Outdoor Unit Installation; Installation Dimension - Sharp AY-X36RU Manuel D'installation

Masquer les pouces Voir aussi pour AY-X36RU:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5

OUTDOOR UNIT INSTALLATION

Installation dimension
Referring to the figure, firmly fasten the
outdoor unit with bolts.
Connecting the drain hose
In the heating mode, the outdoor unit discharges water due to defrosting from its
drain hole. Perform drain work if water drops are a problem.
(1) Insert the base pan cap and the drain hose adapter into the drain holes on the
bottom of the outdoor unit.
(2) Connect commercial drain hose to the drain hose adapter.
Notes:
• In very cold areas where the water in the drain hose could freeze, do not use the
base pan cap, the drain hose adapter and a drain hose with the outdoor unit.
6
CONNECTING THE REFRIGERANT PIPES
Flaring the pipe end
(1) Cutting with a pipe cutter
Cut at a right angle.
(2) Deburring
Allow no cuttings in the pipe.
(3) Putting in the flare nut
Use the flare nut included in the accessories.
(4) Flaring
Flare processing dimensions(A)
Tool
0-0.02 inch
R410A tool
(0 - 0.5 mm)
Conventional
0.04-0.06 inch
tool
(1.0 - 1.5 mm)
(5) Checking
To be flared perfectly circular.
Flare nut not missing.
7
AIR REMOVAL
Use a vacuum pump, gauge manifold and hoses exclusively for R410A.
(1) Remove both valve shaft caps of the 2 and 3-way valves.
(2) Remove the service port cap of the 3-way valve.
(3) Connect the gauge manifold hose to the service port and the vacuum
pump.
Be sure that the hose end to be connected to the service port has a
valve core pusher.
(4) Open the gauge manifold low-pressure valve(Lo) and operate the
vacuum pump for 10-15 minutes.
Make sure the compound gauge reads -0.1 MPa(-76 cmHg)(-30
in.Hg).
(5) Close the gauge manifold valve.
(6) Turn off the vacuum pump.
Leave as it for 1-2 minutes and make sure the needle of the com-
pound gauge does not go back.
(7) Open the 2-way valve 90° counterclockwise by turning the hexagon
wrench. Close it after 5 second, and check for gas leakage.*
(8) Disconnect the gauge manifold hose from the service port.
(9) Fully open the 2-way valve with hexagon wrench.
(10) Fully open the 3-way valve with hexagon wrench.
(11) Firmly tighten the service port cap and both valve shaft caps with a
torque wrench at the specified tightening torque.
* Check the pipe connections for gas leak using a leakage detector or
soapy water. Regarding leakage detector, use high-sensitivity type de-
signed specially for R410A.
AYX36RU_IM_3_lang.indb 4
24 inch (609 mm)
Connecting the pipes
Connect the pipes for the indoor unit first and then for the outdoor unit.
90°
For indoor unit, remove sealing cap from the pipe end.
(1) Tighten the flare nuts by hand for the
(2) Use a spanner and torque wrench to
(3) Apply the accompanying insulation
A
A
15.7 inch (399 mm)
Drain hole (for the drain hose adapter)
Drain hole (for the base pan cap)
7 BASE PAN
CAP
first 3-4 turns.
tighten up the pipes.
• Do not over tighten the pipes. It
may be deformed or damaged.
to pipe joints to prevent condensa-
tion.
Flare nut tightening torque
Pipe size
Liquid
1/4" (ø 6.35 mm)
side
Gas side
5/8" (ø 15.88 mm)
3-way valve
Service port
Service port cap
2-way valve
Valve shaft cap tightening torque
Pipe size
Liquid side
Gas side
Service port cap tightening torque
Torque
5.9 ft·lbs(8 N · m)
GB-4
6 DRAIN HOSE ADAPTER
Drain hose
(Commercially available)
Flare nut
Spanner
Torque wrench
8 INSULATION
Torque
11.1-14.8 ft·lbs (15-20 N·m)
44.3±47.9 ft·lbs (60-65 N·m)
Gauge manifold
Compound gauge
Lo
Valve shaft cap
Vacuum pump
Hexagon wrench
(Diagonally 5 mm)
CLOSE
OPEN
Torque
1/4"
14.8-15.5 ft·lbs (20-21 N · m)
5/8"
22.1-23.6 ft·lbs (30-32 N · m)
2014-09-12 07:59:34
Hi

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ae-x36ru

Table des Matières