Installing The Mounting Plate; Connecting The Cable To The Indoor Unit - Sharp AY-X36RU Manuel D'installation

Masquer les pouces Voir aussi pour AY-X36RU:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

PIPING
Max. piping
Max. height
length:A
difference:B
98.4 ft (30 m)
32.8 ft (10 m)
• Standard piping length is 24.6 ft (7.5 m).
• When the outdoor unit is placed at a higher level than the indoor unit, provide a trap near the hose's lead-in port.
Use the refrigerant pipes shown in the table below.
Pipe size
Liquid side
1/4" (ø 6.35 mm)
Gas side
5/8" (ø 15.88 mm)
• The thermal insulation should cover both the gas and liquid pipes.
1
PLACING THE MOUNTING PLATE AND MAKING A PIPING HOLE
Installing the mounting plate
(1) Referring to the the figure below,
mark the location for the fixing holes
and the piping hole.
• Make sure that the mounting plate
is horizontally.
(2) Secure the mounting plate to the wall
with the long screws and check the
stiffness.
Making a piping hole
(1) Drill a piping hole with concrete drill or a hole saw with
a 0.2 inch (5 mm) down ward slant to the outside.
Diameter: 2.6inch (65mm)
(2) Set the sleeve and caps.
2

CONNECTING THE CABLE TO THE INDOOR UNIT

• Use a solid or stranded wire.
Connecting cable: AWG14
• Use copper wire.
• Follow local electrical codes.
• Use a double insulated cable with 600 V insulation.
(1) Process the end of the connecting cable for the
indoor side.
(2) Attach the conduit connector to conduit holder with
the lock nut.
(3) Insert the cable into the unit through the conduit con-
nector.
(4) Open the open panel.
(5) Remove the cable holder.
(6) Connect the cable.
(7) Fix the cable with the cable holder and the screw.
(8) Put back the cable cover.
(9) Close the open panel.
Cable cover
Cautions:
• Be very careful not to confuse the terminal connections. Wrong cabling may damage the internal control circuit.
• Be sure to connect the cable to match the markings on the indoor unit's terminal board and those of the outdoor unit.
• Be sure to put the cable leads deep into the terminal board and tighten up the screws. Poor contact can cause overheating or fire, or
malfunction.
• Be sure to use a disconnect switch. Follow the local and state electrical codes.
AYX36RU_IM_3_lang.indb 2
Min. piping
Additional refrigerant
length
Piping length exceeds 24.6 ft (7.5 m)
9.8 ft (3 m)
0.5 oz/ft (50 g/m)
Pipe thickness
0.03 inch(0.8 mm)
Thickness: 0.24inch (6 mm) or thicker
Material: Polyethylene foam
0.04 inch (1.0 mm)
9.8 (248)
2 (51)
4 (102)
Center of wall hole
Conduit connector
L1' S
Screw
Thermal insulation
52.2 (1327)
29.4 (746)
Outline of indoor unit
Wall
Outdoor
Indoor
Cut with a saw.
Cap
0.2 inch (5 mm)
Sleeve
(Downward to outdoor)
In case using solid wires
Stripping length: 0.7 inch (18 mm)
Be sure to make the wire hook-shaped.
Lock nut
Copper wire
Conduit holder
In case using stranded wires
Stripping length: 0.3 inch (8 mm)
For power supply cable, securely clamp a round
terminal to each end of the stripped wire.
Terminal board
L2'
G
Copper wire
Earth wire
Connecting cable
GB-2
A
B
B
Trap
13.1 (333)
11.3 (286)
1.6 (41)
Center of wall hole
Length unit: inch (mm)
2.4 inch (60 mm)
2.0 inch (50 mm)
Earth wire
0.7 inch (18 mm)
0.3 inch (8 mm)
Round terminal
2014-09-12 07:59:33