Télécharger Imprimer la page

CEMO KS-Mobil 400 l Manuel D'utilisation page 26

Publicité

Les langues disponibles
  • FR

Les langues disponibles

GB
6. Maintenance and inspection
6.1 Safety measures
i
Important!
The operator must provide any protective
clothing that may be required.
Who can carry out maintenance and inspection
work?
» Normal maintenance work may be carried out by
operational personnel.
6.2 Maintenance and inspection table
Interval
Assembly
As
Outside of fil-
required
ling station
Container
Piping
Monthly
system
Leakage
indicator
Moving parts
of the tank
Annually
Leakage
indicator
2,5 yearly
Filling station
5 yearly
Filling station
6.3 Explanations on recurrent checks
and inspections
The CEMO KS-Mobil 400 l / 600 l / 980 l must be
inspected by an officially recognised expert**
accordance with ADR 6.5.4.4.1 a) at intervals of not
more than 5 years . This inspection must check
conformity to type, including the labelling as well as
the internal and external condition and the correct
operation of the operating equipment, and must
satisfy the responsible authority.
The tank must also be inspected by an expert* in
accordance with ADR 6.5.4.4.1 b) at intervals of at
most two and a half years . This inspection must
* Experts are specialists. They are able to assess the operational safety condition of equipment by virtue of their
training and experience.
** Officially recognised experts are specially trained, officially recognised experts. Officially recognised experts have
the task of testing facilities, technical devices and equipment at set intervals and issuing a report of their findings.
26
All manuals and user guides at all-guides.com
Action
Clean off any stuck-on dirt or fuel.
Repair damage to the galvanisation through cold galvanising.
Visual inspection for damage
Check hoses for cracks and porosity, check
fittings for leaks (replace defective parts).
Visual check of the level in the glass cylinder.
If it changes, see operating instructions for "Leakage indicator"
Lubricate hinges and closure with a few drops of universal oil.
Function test. Flow rate of leaking liquid at test valve e 0.5 l/min,
see operating instructions for "Leakage indicator"
Inspection by experts*:
- Documentation in the test report (see section 9)
- For successful inspection – Imprint on type plate (month/year, e.g. 01/16)
Inspection by officially recognised expert**
- Documentation in the test report (see section 9)
- For successful inspection – Imprint on type plate (month/year, e.g. 01/16)
i
Important!
Inspections of the filling station may only
be performed by experts* or officially
recognised experts**.
check the external condition and correct operation
in
of the operating equipment, and must satisfy the
responsible authority.
In accordance with ADR 6.5.4.4.2, all metal IBCs for
transporting liquid substances must be subjected to an
initial inspection (i.e. before the IBC is used for trans-
portation for the first time) following repair and leak
testing at intervals of at most two and a half years .

Publicité

loading

Ce manuel est également adapté pour:

Ks-mobil 600 lKs-mobil 980 l