APPLICABLE CONTROLS
Setup of external static pressure
Matching with the resistance (External static pressure) of the duct to be connected, be sure to set up the tap
exchange according to the basic operation procedure (
• For the item code in Procedure
• For the set data in Procedure
data of static pressure outside of the machine to be
set up from the table on the right.
To incorporate a filter sold separately
When mounting a filter sold separately, be sure to set up the tap exchange according to the type of filter.
In this case, also follow to the basic operation procedure (
• For the item code in Procedure
• For the set data in Procedure
data of filter to be incorporated from the table below.
• Select with shifting of the short plug on the
indoor unit microcomputer P.C. board.
Short plug position
External static
pressure
40Pa
Standard
(At shipment)
70Pa
High static-
pressure 1
100Pa
High static-
pressure 2
20Pa
Low static-
pressure
*1 Resistance of high-performance filter 65 and 90 is
equivalent to 30Pa.
Therefore, set the resistance (external static
pressure) of a duct to be connected to 40Pa.
All manuals and user guides at all-guides.com
1
3
, specify [5d].
4
, select the setup
3
, specify [5d].
4
, select the setup
Filter sold separately
Standard filter
(At shipment)
*1
High-performance filter 65
High-performance filter 90
Never execute such a
change of the short plug
as shown at the left;
otherwise a malfunction
may be caused.
23
2
3
4
5
6
).
(Exchange by wired remote controller)
Set data
External static pressure
0000
40Pa
0001
70Pa *1
0003
100Pa *2
0006
20Pa
1
2
3
4
5
6
Set data
0000
Standard filter (At shipment)
0001
High-performance filter 65, 90
• Short plug position
(CN112, CN111, CN110 from the left)
Standard (At shipment)
High static pressure 1
High static pressure 2
Low static pressure
*1: For SM1402BT, set 65Pa.
*2: For SM1402BT, set 90Pa.
).
Filter sold separately