7.2. LCD DISPLAY FUNCTIONS.
When starting the UPS, the display shows the summary screen of
its default status.
Main
Submenu
menu
UPS status
Event log
Measure-
ments
Start battery test Start manual battery test
Start WLAN
configuration
Finish WLAN
configuration
Reset fault
Control
status
Reset event list
Reset
integrated IoT
Restore factory
settings
Settings
Identifica-
tion
Tab. 16. Default UPS statuses.
7.3. USER SETTINGS.
Submenu
Password
It can be changed by the user.
Change
English, Italian, French, German,
language
Spanish, Polish, Catalan, Portuguese
User password
[Enabled, ****], [Disabled]
Audible alarms
[Enabled], [Disabled]
Output voltage
[220 V], [230 V], [240 V]
Output
[Normal auto detect],
frequency
[50 Hz, 60 Hz converter]
High efficiency
[Enabled], [Disabled]
mode
Auto Bypass
[Enabled], [Disabled]
78
Display information or menu function
UPS mode, IoT status, date/time, battery
status and current alarms
Shows stored events and faults
[Load] W VA AP%, [Input/Output] V Hz,
[Battery] % min V EBM, [DC Bus] V,
[Temperature] C
If the WLAN status is in configuration mode,
the available option will be "Finish WLAN
configuration", otherwise the available
option will be "Start WLAN configuration"
Clear active fault
Clear events and faults
Reset the IoT and modbus TCP function in
the UPS
Reset to factory default settings
See user settings
[Product type], [Model], [Serial number],
[UPS firmware], [Embed IoT firmware],
[Embed Ethernet IP], [WLAN IP],
[Embed Ethernet MAC], [WLAN MAC]
Available settings
Default settings
0000
English
[Enabled]
[Enabled]
[230 V]
Normal automatic
detection
50 Hz/60 Hz
[Disabled]
[Enabled]
Submenu
Available settings
Cold start: [Disabled], [Enabled]
Start / Restart
Auto restart: [Disabled], [Enabled]
Wiring fault
[Enabled], [Disabled]
Overload
[50%÷105%]
pre-alarm
[Auto-detection],
[Manual EBM: 0÷12]
External battery
[Manual Ah: 0÷300 Ah]
[No battery]
1÷4 A for 4÷10 kVA
Charger current
2÷12 A for 6÷10 kVA
[Disabled], [Remote activated],
Dry in signal
[Remote deactivated], [Forced bypass],
[Remote MBP]
[load powered], [on batt.], [batt. low],
Dry out signal
[batt. open], [bypass], [UPS ok]
Ambient temp.
[Enabled], [Disabled]
alarm
Remaining
[Enabled], [Disabled]
battery time
Date and time
dd/mm/yyyy hh:mm
Time zone
Set time zone
LCD contrast
[0-100%]
Modbus TCP
[Enabled], [Disabled]
Enable internal
[Yes], [No]
IoT
Tab. 17. User settings
7.4. DESCRIPTION OF THE LCD DISPLAY.
The LCD backlight automatically dims after 10 minutes of inactivity.
Press any button to restore the screen, except the on/off button.
Fig. 60. SALICRU logo.
The logo graphic above is the default screen during logical
power-up and is displayed for the first 5 seconds. After this time,
the status screen or the first start menu appears if the unit is being
started up for the first time.
The control buttons have no effect during these first 5 s.
Default settings
enabled
enabled
[Disabled]
105%
Auto detection
0 branches
(for MB TWIN
PRO3 EBM,
2 branches =
1 modular EBM)
0 Ah
1.4 A for 4÷6K
2 A for 8÷10K
4 A for 6÷10K B1
[Remote MBP]
[on batt.]
[Enabled]
[Enabled]
01/01/2022 00:00
GMT+1
50%
[Disabled]
[Yes]
SALICRU