Appendix

12. Appendix

12.1 FAQs

QUESTION
Is it possible to connect two
heating circuits to a "Unibox
T RTL"?
How many m² of surface
temperature balance can I
connect to the "Unibox T
RTL"?
Can the "Unibox T RTL" be
operated using an actuator?
36
RESPONSE
Yes, use a "Duo connection piece" to connect two heating
circuits of the same size to one "Unibox T RTL". Each surface
temperature balance circuit may have a maximum pipe length
of 80 m, provided you use 16/17 mm pipes.
Illustr. 13: Connection diagram with two heating circuits using
"Duo connection piece"
You can connect a surface covering approximately 20 m² to
each "Unibox T RTL". The pipe length must not exceed 100 m
when using a 17 mm pipe.
Yes, the "Unibox T RTL" can be operated using an actuator.
The actuator is mounted on the connection for the control
piston. You must use a closed cover plate when operating the
product with an actuator.
Unibox T RTL
102273380-V01.06.2019