Troubleshooting
9.
Troubleshooting
MALFUNCTION
Surface temperature balance
does not get warm.
34
CAUSE
The "Unibox T RTL" is in-
stalled in the supply.
Illustr. 12: "Unibox T RTL"
installed in the
supply
Problems with the heating
system/heat generator.
The Duo connection piece for
two heating circuits is being
used (see Illustr. 13 on page
36).
Unibox T RTL
REMEDY
Swap the inner components
of the "Unibox T RTL" with the
inner components of the "Uni-
box ET" (Item no. 1022632).
Increase the pump output (if
possible).
Check the resistances of the
heating circuits. All heating
circuits must have the same
resistance.
102273380-V01.06.2019