4.6 Protocolo ModBus RTU
É relatado, a seguir, o elenco de comandos para a transmissão de dados via Porta Serial RS485 RTU
> Read Holding Register
> Write Multiple Register
> Report Slave ID
O sistema responde ao comando Report Slave ID com uma cadeia de caracteres:
"Device"+ Firmware code + Edition
ModBus profile table Address
Description
Property
1000
pH Measure
1001
Cl Measure
1002
Orp Measure
1003
Temperature Measure
1004
Frequency Measure
1005
Conductivity Measure
1006
Pot1 Measure
1007
Pot2 Measure
1008
Status
1100
SetPoint pH
1101
SetPoint Cl
1102
SetPoint Orp
1103
SetPoint Temperature
Note1: STATUS (bit field 16 bit register)
1
LEVEL_0_ALARM
2
LEVEL_1_ALARM
3
HOLD_ALARM
4
REED_ALARM
5
Reserved
6
Reserved
7
Reserved
8
Reserved
9
Reserved
10
Reserved
11
Reserved
12
Reserved
13
STAT (Wieving statistics Mode)
14
Reserved
15
OFA (Over Feed Alarm)
16
PERMANECY (Permanency Allarm)
Range
Read 0 to 1400
Read 0 to 500
Read -2000 to +2000
Read 0 to 1050
Read 5 to 15000
Read 0 to 10000
Read 0 to 20000
Read 0 to 20000
Read See Note 1
Read/Write 0 to 1400
Read/Write 0 to 500
Read/Write -2000 to +2000
Read/Write 0 to 1050
0000137242
Rev.3.1
Operating state
Full Operating
Full Operating
Full Operating
Full Operating
Readable but not active
Readable but not active
Readable but not active
Readable but not active
Full Operating
Full Operating
Full Operating
Full Operating
Full Operating
26