Cable types and minimum thicknesses
Cable length (m)
Power supply 230 V AC
24 V AC/DC flashing beacon
TX Photocells
RX photocells
Command and control devices
* no. = see product assembly instructions - Warning: the cable cross-section is indicative and varies according to the motor power and cable length.
When operating at 230 V and outdoors, use H05RN-F cables compliant with 60245 IEC 57 (IEC); when operating indoors, use H05VV-F cables compliant with
60227 IEC 53 (IEC). For power supplies up to 48 V, you can use FROR 20-22 II cables compliant with EN 50267-2-1 (CEI).
To connect the antenna, use RG58 cable (up to 5 m).
For paired connection and CRP, use UTP CAT5 cable (up to 1,000 m).
If the cable lengths differ from those specified in the table, define the cable cross-sections according to the actual power draw of the connected devices and in
line with regulation CEI EN 60204-1.
For multiple, sequential loads along the same line, recalculate the values in the table according to the actual power draw and distances. For information on
connecting products not covered in this manual, please see the documentation accompanying the products themselves.
BUS cable table
We recommend using a FROR 2x1mm² cable, maximum length from the control board: 50 m.
Single branch length (m)
BUS cable
The total length of all branches can be a maximum of 150 m.
The cable cannot be shielded.
up to 20
3G x 1.5 mm2
2 x 1 mm2
2 x 0.5 mm2
4 x 0.5 mm2
* no. x 0.5 mm2
from 20 to 30
3G x 2.5 mm2
2 x 1 mm2
2 x 0.5 mm2
4 x 0.5 mm2
* no. x 0.5 mm2
max. 50 m
2 x 1 mm²