4.2
Check the generating set is in a good general condition (bolts, hoses)
Inspect the entire generating set before start-up and after each use to prevent any faults or damage.
1.
Check that there is no fluid or debris in the retention container (A7): if necessary, pump the fluid into a suitable container.
Any fluids present in the retention container (rainwater, engine oil or fuel) must be recycled or eliminated according to the local regulations
in force.
2.
Check all the pipes and hoses to ensure they are in good condition and that there are no leaks.
Pipes or hoses must be replaced by a specialist technician. Please contact your nearest agent
3.
Tighten any loose nuts or bolts.
The cylinder head bolts must be retightened by a specialist technician. Please contact your nearest agent.
4.3
Check the coolant level
1.
Fill up when the unit is switched off and the engine cold.
If the unit has been used, leave to cool for at least 30 minutes
2.
Open the coolant filler cap (A1) by loosening it slowly.
3.
Visually check the level. It should just cover the harness.
4.
If the level is too low, top up using a funnel and coolant that complies with the specifications contained in this manual.
There should be no coolant in the neck. In case of overfilling, pump off the excess into an appropriate container.
5.
Carefully close the cap and wipe away any trace of coolant.
4.4
Checking the engine oil level and topping up
1.
Fill up when the unit is switched off and the engine cold.
If the unit has been used, leave to cool for at least 30 minutes
2.
Remove the dipstick (A8-B1) and wipe it.
3.
Reinsert the dipstick then remove it again.
4.
Visually check the level. It should be between the upper limit (B2) and the lower limit (B3) marked on the dipstick.
If the oil level is too low: open the oil filler cap (
If the oil level is too high: drain some of the oil into a suitable container.
5.
Check the level again before screwing the dipstick back in.
6.
Check that there are no oil leaks, and wipe away any traces of oil with a clean cloth.
4.5
Checking the fuel level and topping up
Visually check the fuel level using the fuel level indicator (A10). If necessary, fill with fuel:
1.
Fill up when the unit is switched off and the engine cold.
2.
Unscrew the fuel tank cap (A11).
3.
Fill the fuel tank using a funnel, taking care not to spill any.
Do not overfill the tank (there should not be any fuel in the filler neck).
4.
Screw the fuel tank cap back on.
5.
All traces of fuel should be wiped off with a clean cloth.
4.6
Starting the generating set
Once the daily checks have been performed, and having read the instructions and safety regulations carefully:
1.
Open the fuel tap (A12).
2.
It is essential to close the top cover and the access door to the generating set.
3.
Turn the key (A15) to the "ON" position: all the indicator lights on the APM202 (A16) light up briefly.
4.
Press the "START" button once: after a few seconds, the generating set starts up.
The APM202 automatically performs 3 starting attempts. If the generating set does not start after these 3 attempts, see the section on
Resolving minor faults.
4.7
Using the electricity supplied
1.
Allow the unit speed to stabilize and the temperature to rise (approx. 3 to 5 min.).
2.
Connect the equipment to be used to the electrical sockets (A17) on the unit.
For three-phase generating sets, use the three-phase electrical socket 3P+N+E in the first place (single-phase electrical sockets are
auxiliary sockets that should only be used occasionally and individually).
3.
Use the working hours counter (A18) to monitor the running time of the unit.
For France only: Our units are fitted with sockets where the earthing contact is made using side tabs.
In exceptional cases where the equipment is only fitted with an earthing pin, use an adaptor. After use,
always disconnect the adaptor and store it carefully, away from sources of moisture. Always ensure
that the socket cover on the unit is closed: risk of damage (loss of seal).
4.8
Switching the generating set off
1.
Disconnect the electrical connectors (A17) taking care to close the socket cover on the generating set.
2.
Allow the generating set to run without any load for 1 to 2 minutes.
3.
Turn the key (A15) to the "OFF" position: the generating set stops.
4.
Open the access door to the generating set in order to close the fuel tap (A12).
5.
Close the access door to the generating set.
6.
Ensure the unit is properly ventilated and to avoid any risk of fire, wait for it to be fully cool before covering it and storing it.
Even when the unit is turned off, the engine continues to give off heat.
If the generating set is used with a remote cranking system (remote control or push-button), it remains on standby while the key is
in the "ON" position and draws a low level of power from the battery. Turn the key to "OFF" when the generating set is not in use.
1664_EN.docx
A9
), use a funnel to top up the oil, then screw the oil filler cap back in.
19/270
.
Earthing pin. Use
Side earthing tabs:
the adaptor.
2021-07-01