oPeratIon
Programming
>
 Menu Timer
1 2
LCD
Dénomination
Description
Main Failure
Delays priority network failure detection
timer
1 2
Delay on
Standby network stability validation before transfer
transfer timer
1 2
O Main failure
Rest in O position when transferring
timer
from main network to secondary network
1 2
Main return
Main network stability validation before re-transfer
timer
1 2
O main return
Rest in O position when re-transferring from standby
timer
network to main network
1 2
Cool down
Allows generator cooling down period after load's
timer
retransfer from standby source (generator) to Main source
1 2
52
All manuals and user guides at all-guides.com
oPeratIon
Plage
Valeurs
de
par
réglage
défaut
From 0
5 s
to 60 s
From 0
5 s
to 60 s
From 0
0 s
to 20 s
From 0
2 min
to 30 min
From 0
0 s
to 20 s
From 0
4 min
to 10 min
Programming
>
 Inputs / Outputs Menu
1 2
Output relays are NO type (construction) and can not be
configured as NC.
Input state can be configured: NC or NO.
LCD
Denomination / Definition
Input 1
1 2
Input 1 state
1 2
Input 2
1 2
Input 2 state
1 2
output 1
1 2
output 2
1 2
53
Setting range
Default
values
Ft1, Ft2, Ft3, Ft4,
/
Pri, Mtf, / S2A,
MAN, CtS, tol,
tfl, EJP
NO, NC, /
No
Ft1, Ft2, Ft3, Ft4,
/
Pri, Mtf, / S2A,
MAN, CtS, tol,
tfl, EJP
NO, NC, /
No
S1A, S2A, LS, /
/
S1A, S2A, LS, /
/