ConneCtIonS
Control circuits
Denomination
terminals Description
N (103)
Neutral

Power supply

L3 (104)
Phase 3
L2 (105)
Phase 2
L1 (106)
Phase 1
L1 (203)
Phase 1
Power supply
L3 (205)
Phase 3
Genset
13
Genset start / stop relay - 2 stable positions
(1)
start signal
14
Programmable state - factory setting - = NO, close
to start
Control
23
Impulse mode: order to close source
(impulse,
Contactor mode: order to close contactor source
24
contactor and
Breaker mode: order to close breaker source
breaker mode to
programm)
33
Impulse mode: order to close source
34
Contactor mode: order to close contactor source
reaker mode: order to close breaker source
43
Impulse mode: order to reach position 0
Contactor mode: programmable relay O1
44
Breaker mode: order to open breaker source
53
Impulse mode: programmable relay O2
Contactor mode: programmable relay O2
54
Breaker mode: order to open breaker source
Information
301
Auxiliary contact information position 1 CA1
auxiliairy
302
Auxiliary contact information position 0 CA0
contacts
303
Auxiliary contact information position 2 CA2
Programmable
304
Programmable input In1
inputs
305
Programmable input In2
Common input
306
Specific voltzge supply
Common terminals 301 à 306
Remote
RJ
Remote interface
interface
connection
(1) Refer to programming, Setup, to modfy relay state.
42
All manuals and user guides at all-guides.com
ConneCtIonS
Characteristics
Recommended
section
440 V ac
1,5 mm
2
(phase - phase)
maximum,
50 / 60 Hz 254 V
ac (phase neutral)
maximum,
50 / 60 Hz
440 V ac
1,5 mm
2
(phase - phase)
maximum
Contact sec libre
1,5 mm
2
de potentiel 5 A
AC1 / 250 V
5 A AC1 / 250 V
1,5 mm
2
5 A AC1 / 250 V
1,5 mm
2
5 A AC1 / 250 V
1,5 mm
2
5 A AC1 / 250 V
1,5 mm
2
Do not connect to
1,5 mm
2
any power supply
Do not connect to
1,5 mm
2
any power supply
Do not connect to
1,5 mm
2
any power supply
Maximum
RJ45 8 / 8
connection cable
3 m

electrical operation

power supplY
the products integrate 2 power inputs (104 - 106,
203 - 205), and consider the available source to keep
the product operational. Product supplied when volt-
age on terminals ≥ 100 Vac.
43
: terminals 104 - 106
: terminals 203 - 205