oPeratIon
Programming
>
  Inputs / Outputs Menu
1 2
inputs
Variable
Description
Ft1
Fault input 1. the fault led is blinking as soon as the input is active and
Ft1 is displayed on LCD. Reset when the input is de-activated
Ft2
Fault input 2. the fault led is blinking as soon as the input is active and Ft2 is displayed on
LCD. Reset when the input is de-activated
Ft3
Fault input 3. the fault led is blinking as soon as the input is active and Ft3 is displayed on
LCD. the transfer switch is immediately driven in 0 position (only in contactor mode). Keypad
action (Validation) necessary to Reset the fault
Ft4
Fault input 4. the fault led is blinking as soon as the input is active and Ft4 is displayed on
LCD. the transfer switch is immediately driven in 0 position (only in contactor mode). Keypad
action (Validation) necessary to Reset the fault
Pri
(1)
Priority network selection.
Network 1 has priority when input is not activated. Network 2 has priority if input is active
Mtf
Remote manuel re-transfer. Feature identical to manual retransfer on keypad.
Re-transfer from priority network to backup network is allowed from input activation (1s front).
the Mtf variable in the setup menu must be selected (Yes) to allow input recognition
S2A
Information source
available (Genset) used instead of voltage / frequency measurement
(inhibited when S2A is selected)
Man
Information transfer system in manual mode
All automatic commands (+ test on load) are inhibited as soon as the input is activated
CtS
Remote transfer control. Possible to initiate transfer from priority source to backup source
before Dtt ends. If Dtt is set to its maximum value (60s), the transfer is initiated as soon as
the input is activated (1s front)
tol
Remote test on load. Started from input activation.
Re-transfer is blocked until input de-activation
tfl
Remote test off load
Started from input activation (remote genset start / stop)
EJP
2 inputs are automatically affected to EJP
• input 1 for EJP advice, to start generator
• input 2 to transfer on emergency source
Retransfer is activated when input 2 dissapears
(1) this information is the only considered in case of
option configuration. Programming variable Pri is then
inhibited.
• eJP cycle
EJP advice (input 1)
EJP transfer (input 2)
Start generator
DTT
Source 1
OMF
OMR
Source 2
54
All manuals and user guides at all-guides.com
CDT
oPeratIon
Programming
>
  Inputs / Outputs Menu
1 2
outputs
Variable
Description
S1A
Source
available.
Output activated as soon as source
S2A
Source
available.
Output activated as soon as source
LS
Load shedding relay. LS timer corresponds to time available to disconnect the shed loads.
the relay is activated before permutation on standby network according to LS timer.
the relay is de-activated after retransfer on mains network and LS timer countdown
In case of LS function selection, it is required to configure associated LS timer.
Output
Function
S1A, S2A, LS, /
1 2
1 2
• example : LS configuration (output relay Ou1, 3 seconds):
the load shedding can't be used with the priority net-
work (priority source = source
). In this case, LS
output is not valid.
• load shedding cycle
Dtt timer
Priority source -
emergency source
transfer
ls timer
Position II (emergency) AC activation
LS
AC II
Load shedding output
the output is de-activated in case of loss of power. It may then be required to put in
parrallel with the load shedding ouptut relay, position 2 auxiliary contact. this would avoid
taking back the load in case of loss of emergency source in emergency position.
55
is considered available (similar to front led source
is considered available (similar to front led source
Setting range
Default Value
For LS:
For LS :
0 to 60 s (≤ Dtt)
3 s
1 2
1 2
Emergency source
- priority source
ls timer
transfer
LS relay Activation
)
)