oPeratIon
Programming
>
 Volt menu
1 2
threshold detection starts from the loss of source
or source return sequence.
LCD
Denomination / Definition
Network
over voltage threshold
1 2
Network
over voltage threshold hysteresis
1 2
Network
under voltage threshold
1 2
Network
under voltage threshold hysteresis
1 2
Network
over voltage threshold
1 2
Network
over voltage threshold hysteresis
1 2
Network
under voltage threshold
1 2
Network
under voltage threshold hysteresis
1 2
Values definition: % of nominal values.
Hysteresis values range is limited by thresholds values.
50
All manuals and user guides at all-guides.com
oPeratIon
Setting range
Default
values
From 102 to 120 % 115 %
From 101 to 119 %
110 %
(< ou)
From 80 to 98 %
85 %
From 81 to 99 %
95 %
(> uO)
From 102 to 120 % 115 %
From 101 to 119 %
110 %
(< ou)
From 80 to 98 %
85 %
From 81 to 99 %
95 %
(> uu)
Programming
>
 Frequency Menu
1 2
threshold detection starts from the loss of source
or source return sequence.
LCD
Denomination / Definition
Network
over voltage threshold
1 2
Network
over voltage threshold hysteresis
1 2
Network
under voltage threshold
1 2
Network
under voltage threshold hysteresis
1 2
Network
over voltage threshold
1 2
Network
over voltage threshold hysteresis
1 2
Network
under voltage threshold
1 2
Network
under voltage threshold hysteresis
1 2
Values definition: % of nominal values.
Hysteresis values range is limited by thresholds values.
51
Setting range
Default
values
From 101 to 120 % 105 %
From 100,5 to
103 %
119,5 % (< oF)
From 80 to 99 %
85 %
From 80,5 to
97 %
99,5 %
(> uF)
From 101 to 120 % 105 %
From 100,5 to
103 %
119,5 % (< oF)
From 80 to 99 %
95 %
From 80,5 to
97 %
99,5 %
(> uF)