System Type - Parameters Menu
23 parameters are available, indicated by the letter "P." which are not modifiable from Remote Timer Control.
Parameter
P.01
Heating request selection
P.02
Cascade sensor selection
P.03
No function
P.04
3-way valve time
P.05
Activation timer*
P.06
Deactivation timer*
P.07
Activation power*
P.08
Deactivation power*
P.09
Hydraulic separator function
P.10
System filling function
P.11
3-way valve selection
0-10Vdc Heating OFF voltage (Temperature
P.12
Control)**
0-10Vdc Heating ON voltage (Temperature
P.13
Control)**
0-10Vdc Max. voltage (Temperature Con-
P.14
trol)**
0-10Vdc Min. temperature (Temperature
P.15
Control)**
0-10Vdc Max. temperature (Temperature
P.16
Control)**
0-10Vdc Heating OFF voltage (Power Con-
P.17
trol)**
0-10Vdc Heating ON voltage (Power Con-
P.18
trol)**
P.19
0-10Vdc Max. power (Power Control)**
P.20
0-10Vdc Min. power (Power Control)**
P.21
0-10Vdc Max. power (Power Control)**
P.22
Enable DHW Slave boiler (Autocascade)
Continuous comfort Slave boiler
P.23
(AX5200SQ)
Notes
1. * These parameters are active only when several systems are connected in cascade.
2. ** These parameters are active only when the system operates with input 0-10Vdc.
192
Description
0 = Normal heating request
1 = Request from remote control with
external on-off enabling
2 = 0-10V signal request with temperature
control with external on-off enabling
3 = 0-10V signal request with external on-
off enabling
4 = Control of 2 climatic curves with remote
control-room thermostat and second room
thermostat
5 = Control of 2 climatic curves with remote
control-room thermostat and second room
thermostat
0 = Disabled
1 = CH + DHW (Heating + DHW)
2 = CH (Heating)
0-1
0 ÷ 255 seconds
0 ÷ 255 minutes
0 ÷ 255 minutes
0 ÷ 100%
0 ÷ 100%
OFF = Disabled, ON = Enabled
OFF = Disabled, ON = Enabled
2/3 = 2 or 3 wires
2 = 2 wires
0.1-10 Vdc
0.1-10 Vdc
0.1-10 Vdc
0 ÷ 100°C
0 ÷ 100°C
0.1-10 Vdc
0.1-10 Vdc
0.1-10 Vdc
0-100%
0-100%
OFF = Disabled, ON = Enabled
OFF = Disabled, ON = Enabled
cod. 3541Z071 - Rev 00 - 06/2022
Range
W 60 W 80 W 99 W 120 W 150
0
0
0
0
1
5
70
25
OFF
OFF
2/3
2.5
3.0
10
20
90
2.5
3.0
10
0
100
OFF
OFF
TORO W
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
5
5
5
5
70
70
70
70
25
25
25
25
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2/3
2/3
2/3
2/3
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
10
10
10
10
20
20
20
20
90
90
90
90
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
10
10
10
10
0
0
0
0
100
100
100
100
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF