Electrical Installation; Technical Data - ABB ACS880-04 Manuel D'installation

200 à 710 kw, 300 à 700 hp
Masquer les pouces Voir aussi pour ACS880-04:
Table des Matières

Publicité

2 Update notice

Electrical installation

CHANGED: Grounding system compatibility check
The standard drive with no EMC filter and the ground-to-phase varistor connected can be
installed to a symmetrically grounded TN-S system. If you install the drive to another system,
you may need to disconnect the EMC filter and ground-to-phase varistor. See ACS880
frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions
(3AUA0000125152
[English]).
WARNING!
Do not install the drive with EMC filter options +E200 and +E202 to a system that
the filter is not suitable for. This can cause danger, or damage the drive.
WARNING! Do not install the drive with ground-to-phase varistor connected to a
system that the varistor is not suitable for. If you do, the varistor circuit can be
damaged.
Corner-grounded and midpoint-grounded 525...690 V delta systems
WARNING!
Do not install the drive on a 525...690 V corner-grounded or midpoint-grounded
delta system. Disconnecting the EMC filter and ground-to-phase varistor does not
prevent damage to the drive

Technical data

CHANGED: Ratings
ACS880-
Frame
Input
04-...
size
current
U
= 500 V
n
503A-5
R10
583A-5
R10
U
= 690 V
n
430A-7
R10
522A-7
R11
650A-7
R11
721A-7
R11
IEC RATINGS
Nominal use
I
I
I
1
max
max_start
A
A
A
505
560
671
585
730
828
430
540
720
522
685
910
650
825
1100
721
825
1100
Output ratings
Light-duty use
I
P
S
I
2
n
n
A
kW
kVA
503
355
436
483
583
400
505
573
430
400
514
420
522
500
624
505
650
630
777
630
721
710
862
705
Heavy-duty use
P
I
Ld
Ld
Hd
A
kW
A
315
361
400
414
400
360***
500
455
630
571**
630
571**
P
Hd
kW
250
250
355
450
560
560