Draw 6 drill marks.
Observe the position of opening "A" for connecting the
current.
WARNING
Wear
safety
equipment
manufacturer's instructions.
Drill holes and blow out with a bellows.
135 mm
270 mm
Check the hole distances.
Hold the ceiling bracket to the ceiling and hammer in
the fastening anchor.
Tighten the fastener according to manufacturer's
instructions.
DANGER
Death hazard from electric shock.
Do not turn on the power supply before the luminaire
head has been installed.
This device must only be connected to a power grid
with a protective ground conductor (PE) to prevent
risk of electric shock
28
A
according
to
the
tool
Connect the power.

3.4. Installing the ceiling tube

A
Pull the ceiling tube cable through the opening "B" of
the ceiling holder.
Insert the ceiling tube "A" into the ceiling holder.
Secure the safety screw "C"and the M8 nut.
D
Tighten the M8 safety screw "C" and the nut (20 Nm).
Tighten all 4 grub screws "D" (5 Nm).
Connect the ceiling tube plug with the power supply
plug.
Slide the ceiling cover and ring over the ceiling bracket
and screw them tight.