Faults
Pos: 170 /Technische Dokumentation/Betriebsanleitung/Störung/Multi/Unzulässige Temperaturerhöhung der Pumpe @ 4\mod_1449582332949_370.docx @ 55497 @ @ 1
Fault: Unauthorised increase in pump temperature
Possible cause
Pump and pipes not
completely ventilated or
filled.
Suction height too
large/Unit's NPSH
(intake) too low.
Flow rate too low.
Pos: 171 /Technische Dokumentation/Allgemeine Module/#### Seitenumbruch #### @ 0\mod_1426069111812_0.docx @ 891 @ @ 1
38 EN
Solution
Vent.
Fill.
Correct liquid levels.
Install pump lower.
Completely open shut-off valve
in the intake.
If the resistance in the intake is
too large, modify the intake line.
Check basket/suction opening.
Observe the permitted pressure
reduction speed.
Increase minimum flow rate.
04/2016