Wiring the device modules
Safety modules
Connections
Pos.
Description
PROFIsafe target address switch (on left side of housing)
X82.1
X82.2
Pluggable terminal strips for input and output signals
X82.3
X82.4
Addressing
An unambiguous PROFIsafe target address ensures that a data telegram reaches the
correct node.
DIP switch 
Value of the address bit
Note!
The combination of a safety module SM300 of version VA 1.08 or higher and a
PROFIBUS communication module of version VB 0.93 or higher makes it
possible to avoid the error that occurs when an address is set to 0. For this
purpose, a defined PROFIsafe target address must be stored in
C13897 or 14897 of the PROFIBUS communication module.

Terminal assignment

X82.1
X82.2
84
1
2
1
2
Labelling
Description
n. c.
n. c.
n. c.
n. c.
n. c.
This terminal strip is not assigned.
n. c.
n. c.
n. c.
n. c.
Labelling
Description
-
GND external supply
+
24 V external supply via a safely separated power supply unit (SELV/PELV)
n. c.
n. c.
This part of the terminal strip is not assigned.
n. c.
n. c.
AIE
Error confirmation input (Acknowledge Input Error)
CLA
Clock output for passive sensors, channel A (clock A)
CLB
Clock output for passive sensors, channel B (clock B)
Labelling
3
4
5
6
4
8
16
32
7
8
9
0
64
128
256
512
EDK94SH104 DE/EN/FR/ES/IT 4.1