7.2
Diagnostics for minor faults
The unit...
Does not start
Stops
Does not function normally
(noise, smoke, etc.)
Does not supply electrical
current
7.3
Replace the protective fuses
The fuses must be replaced in the event of faults caused by overcurrent.
1.
Identify the cause of the fault and the overcurrent (consult one of our agents).
2.
Turn the key (A6) to the "OFF" position: the generating set stops.
3.
Unscrew the fuse holder (A14) and visually check the condition of the two fuses.
4.
Replace any blown fuses with a new fuse with the same technical specifications.
Using an incorrect fuse may result in damage to the unit.
5.
Screw the two fuse holders back in.
7.4
Generator Smart Care
If the unit has been equipped with the "GS101-Generator Smart Care" option (A18),
it is necessary to change the batteries in the Bluetooth GSC101 box when the
warning is displayed in the Generator Smart Care application (approximately every
two years).
1.
Use a small crosshead screwdriver to open the cover of the box,
2.
Remove the used batteries and take them to a waste collection point so
that they can be recycled,
3.
Fit two new AAA batteries, observing the polarity (+/-),
4.
Close the unit cover and carefully tighten the screws.
8.1
Operating conditions
The stated outputs of the units are obtained under the reference conditions outlined in ISO 8528-1(2005):
Total barometric pressure: 100 kPa - Ambient air temperature: 25°C (298 K) - Relative humidity: 30%.
The unit's output is reduced by approximately 4% for every additional 10°C and/or approximately 1% for every additional 100m in
altitude. Units can only operate while stationary.
8.2
Capacity of the generating set
Before connecting and operating the unit, calculate the electrical power required by the units to be used (in watts)*. To ensure
optimal operation, the total wattage of all equipment used at the same time must be:
-
greater than 60% of the rated load for the unit (risk of insufficient load);
-
less than the rated load for the unit during continuous operation (risk of overload).
If the unit is run under or over its rated load frequently or for long periods of time, it can start to wear very quickly. Damage caused
in this way will not be covered by the warranty.
*
This load is usually indicated in the technical specifications or on the manufacturer's plate for the equipment. Some equipment requires a higher
load when starting. This minimum required power must not exceed the unit's maximum power
1085_EN.docx
Check that:
The checks before starting have been
performed.
YES
The battery is correctly connected and
charged.
YES
The equipment to be used has not
been connected prior to starting.
YES
The APM202* fuses are not faulty (the
indicator lights come on).
YES
The oil level is correct.
YES
The fuel level is correct.
YES
Maintenance has been correctly
performed on the unit components.
YES
Have the unit checked by one of our
agents**.
Tripped circuit breaker(s).
YES
The connected devices and their power
cords are not faulty.
YES
Have the unit checked by one of our
agents**.
20/254
Solutions to be applied:
Perform the checks.
NO
Install the battery; replace it with a new
NO
battery if necessary.
Disconnect the equipment then try to start
the unit again.
NO
Have the unit checked by one of our
agents**.
NO
Top up with oil.
NO
Fill up with fuel.
NO
Perform maintenance on the unit as per
NO
the recommendations
Check the capacity of the unit and press
the circuit breakers.
NO
Try with another item of equipment and
NO
another power cord.
** France: 0.806.800.107 (call charge)