Accessories; Connection Flange; Remote Control; Building Management System - Dimplex SI 35TUR Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
4

Accessories

4.1 Connection flange

The device can optionally be switched to flange connection using
the flat-sealing connection flange.

4.2 Remote control

A remote display adds convenience and is available as a special
accessory. Operation and menu navigation are identical to those
of the heat pump manager. Connection takes place via an inter-
face (special accessories) with RJ 12 Western plug.
NOTE
In the case of heating controllers with a removable control panel, this can
also be used directly as a remote display.

4.3 Building management system

The heat pump manager can be connected to a building man-
agement system network via supplementation of the relevant in-
terface plug-in card. The supplementary installation instructions
of the interface card must be consulted regarding the exact con-
nection and parameterisation of the interface.
The following network connections can be made on the heat
pump manager:
Modbus
EIB, KNX
Ethernet
ATTENTION!
If the heat pump or circulating pumps are controlled externally, a flow rate
switch is required to prevent the compressor from being switched on
when there is no volume flow.
EN-4
5
A lift truck is suited for transporting the unit on a level surface.
The device can be lifted from the rear or front on even ground
using a lift truck or fork-lift truck for transportation.
ATTENTION!
The heat pump must not be tilted more than 45° (in any direction).
After transportation, the transport fastening in the device is to be
removed from both sides of the base.
$
$
ATTENTION!
Before commissioning, the transport fastening must be removed.
All panelling can be removed to allow accessing the inside of the
device.
To remove the panelling, open the individual covers by unscrew-
ing the respective screw fasteners and then gently tilting the cov-
ers away from the device. Then lift them up out of the mountings.
452237.66.40 · FD 9610

Transport

SI 35TUR
%
%
www.dimplex.de