4.2 Parameter LEDs description

[(4)]
Referring to Figure 7 in the appendix, use the Parameter
button (3) to change the displayed unit of measurements
during normal operation, following these logical flows:
Power
Parameter
button
Speed
Figure 2
4.2.1 Power
When Power input (active electric power) is the
measurement selected:
• The current power absorbed from the power line
[watts] is displayed on the numeric display (6)
• The W indicator is permanently lit
4.2.2 Flow
When Flow (hydraulic water flow) is the measurement
selected:
• The current water flow estimation gpm (m
displayed on the numeric display (6).
• The gpm (m
/h) indicator is permanently lit.
3
4.2.3 Head
When Head (hydraulic water head) is the measurement
selected:
• The current water head estimation [feet or meters of
water head] is displayed on the numeric display (6).
• The ft (m) indicator is permanently lit.
4.2.4 Speed
When Speed (pump impeller speed) is the
measurement selected:
• The current rotational speed [revolutions per minute] is
displayed on the numeric display (6)
• The rpm indicator is permanently lit
NOTICE
Each hydraulic measure (Flow or Head) can be singu-
larly switched, between ISO and US units of measure,
by pressing the Parameter button (3) continuously for at
least 2 seconds
6
Parameter
button
Flow
Parameter
button
Head
Parameter
button
/h) is
3

4.3 Settings

4.3.1 Set points editing
Referring to Figure 7 in the appendix, use the Setting
buttons (5) to change the set point corresponding to the
currently selected Control Mode (see sec. 4.3.3)
1. Press shortly one of the Setting buttons (5)
The actual set point is shown (blinking) for 4 seconds
on the Numeric display (6), while the relative unit of
measurement is displayed on the Parameter LEDs
(4).
2. Change the value with the Setting buttons (5)
A short button pressure will vary the set point by
one single step, but if the button is kept pressed, the
change will progress automatically in the selected
direction, with an acceleration factor proportional to
the pressed time.
3. Wait 4 seconds to store and activate the new set point
When the change is confirmed, the Numeric display
(6) stops blinking and gets back to the active
measurement which was before entering the
setpoint editing.
NOTE:
During the Set points editing (while the Numeric
display (6) is blinking), pressing the Parameter button
(3) remains ineffective, until the edit operation has been
acknowledged.
4.3.2 Operating modes
Referring to Figure 7 in the appendix, use the Setting
buttons (5) to change the Operating mode from On (fac-
tory default) to Off or vice versa.
4.3.2.1
On ⇒ Off
1. Press shortly one of the Setting buttons (5)
The actual set point is shown (blinking) for 4 seconds
on the Numeric display (6), while the relative unit of
measurement is displayed on the Parameter LEDs
(4).
2. Change the value with the Down arrow button (5), till
reaching the minimum set point
The minimum set point can be easily reached keeping
the Down arrow button (5) continuously pressed.
3. A further short press of the Down arrow button (5)
sets the Off operating mode
When the operating mode is set to Off, on the
Numeric display (6) the message OFF appears
4. Wait 4 seconds to store and activate the new
operating mode
When the change is confirmed, the message OFF
disappears. The Numeric display (6), the Parameters
LEDs (4) and the Control mode LEDs (2) become unlit.
Only the Power, Status and Remote LEDs ((8), (7) and
(9)) remain active according to the description in
sec. 4.1.