Maintenance, Accessories - Tecsis PEX10 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8. Adjustment of zero point / span / 9. Maintenance, accessories
PEX10, PEX11, PEX15:
A
Make sure wires are not cut or pinche during disassembly and reassembly of the connector.
PEX10, PEX11, PEX15: Remove the female connector. Open the pressure sensor by detaching
the clamping nut (see Fig. A ). Carefully remove the male connector from the case.
PEX13, PEX14, PEX15 with field case: Open the pressure sensor by twisting off the fied case over.
Adjust the zero point (Z) (see Fig. B ) by generating the lower limit of the pressure range.
Adjust the span (S) by generating the higher limit of the pressure range.
Check the zero point.
If the zero point is incorrect, repeat procedure as required.
Reassemble the instrument carefully.
Make sure all sealings and o-rings are not damaged and correctly installed to assure the
rated moisture ingress protection.
Recommended recalibration cycle: 1 year

9. Maintenance, accessories

tecsis pressure sensors require no maintenance.
Have repairs performed by the manufacturer only.
40
Betriebsanleitung/Operating instructions/Mode d'emploi/Instrucciones de servicio
Betriebsanleitung/Operating instructions/Mode d'emploi/Instrucciones de servicio
Female
connector
Sealing
Clamping
nut
Male
connector
Sealing
S = Span
Z = Zero
Case with
pressure
connection
PEX13, PEX14,
PEX15 with field case:
B
B
Z = Zero
For further information +49 69 5806-2306
S = Span
GB

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pex11Pex13Pex14Pex15

Table des Matières