Installation and Operation Instructions
CHAPTER 8
SERVICING AND MAIN-
TENANCE
WARNING
NOTE
MiniVent M1/150 F
8.0

Servicing and maintenance

WARNING!
When dismantling, live parts which may result in electric shock upon contact may be exposed.
Before dismantling, isolate the fan from the mains power supply and secure against being switched on again!
– The units are basically maintenance-free, there is no provision for user-maintenance. Nevertheless, all necessary
maintenance work must be carried out by trained electricians!
– Excessive deposits of dirt, dust, grease, etc. on the impeller, motor, protection guard and, above all, between the
housing and the impeller, are not permitted, as these can lead to an unbalance in the impeller, overheating of the
motor or the blocking of the impeller.
– In cases of longer periods of standstill, maintenance must be carried out when the unit is restarted.
The following must be checked:
• Secure mounting of the fan to the subsurface / system, replace in case of doubt
• Remove contaminant deposits
• Mechanical damage, decommission unit, replace damaged parts
• Tightness of screw connections, do not loosen screws in the process!
• Housing surface coating (e.g. rust, paint defects)
• Freewheeling of the impeller -> Is the impeller not running freely- see Fault causes 8.1
• Bearing noises
• Vibrations– see Fault causes 8.1
• Power consumption according to type plate - see Fault causes 8.1
8.1

Fault causes

NOTE!
In case of a blocked impeller or motor, the motor will commence restart attempts in 3 second intervals.
Error/fault
Fan does not start
Fuse blows
Vibrations
Abnormal noises
Fan does not perform
(speed)
Causes
– No voltage
– Defective humidity sensor
– Impeller blocked
– Motor blocked
– Motor just deactivated
– Short-circuited coil in motor
– Supply line/connection damaged Replace parts, replace motor if necessary
– Connected incorrectly
– Contamination
– Mounting-related resonance
– Grinding impeller
– Bearing damage
– Mechanical damage
– Insufficient air supply
– Incorrect voltage
– Bearing damage
– Contamination
– Insufficient backflow
17
Troubleshooting
Check mains voltage
Check connection according to circuit diagram
Contact Helios customer services
Clear blockade, clean, replace impeller if necessary
Contact Helios customer services
Wait for activation guard (15 sec.)
Contact Helios customer services
(Contact Helios customer services)
Check connection, change
Clean
Check/repair mounting
Clean impeller, replace if necessary
Contact Helios customer services
Carry out maintenance
Check/clear inflow and outflow
Check/change connection
Contact Helios customer services
Clean
Enlarge backflow openings