CIAT AirControl CTA Manuel De Régulation page 89

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Configuration
c2
Coil 1
--------
Coil 2
--------
Electric heater
--------
Coil 1 : Hot, Cold or Mixed
Coil 2 : Without, Hot or Cold
Electric heater : Without, 1 stage, 2 stages, 3 stages, Triac, Triac + 1 stage or Triac + 2 stages
Configuration
c3
Recov. unit pressure
--------
Heat recovery unit
----------
Damper
--------
Burner
----------
Recov.: Without, With
Recov.: Without, Plate, Rotary or Rotary F (fixed speed) BG water . ( Media Water glycol )
Damper: Without, With
Burner: Without, Modulating, 2-stage
Configuration
c4
Frost protection th.
--------
Choice of heating coil
---
Control priority
---
Frost protection th.: Without, With
Choice of heating coil: Without, Contact or CMS
Control priority: Precision or Energy optimisation mode
Configuration
c5
Humidity regulation
----
Rh sensor type
------
Adiabatic cooling
---
Humidity regulation: Without, Additional, Dehumidification or Additional + Dehumid.
Rh sensor type: 0-1V, 0-10V
Adiabatic cooling: Without, With
Configuration
c6
Supply air fan
P sensor
------
K -----r
Variable drive ------
Return air fan
P sensor
------
K ------
Variable drive ------
P sensor: 0-1000Pa 10V, 0-2500Pa 10V, 0-5000Pa 10V, 0-1000Pa Ratio, 0-3000Pa Ratio or 0-5000Pa Ratio 0-100Pa 10V,
0-250Pa 10V, 0-500Pa 10V or 0-750Pa 10V.
K: Fan K coefficient value
Variable drive: No, yes
Level 3 access
Level 3 access
Level 3 access
Level 3 access
Level 3 access
EN - 23
EN

Publicité

Chapitres

Table des Matières
loading

Table des Matières