Machine Parameters Menu - CIAT AirControl CTA Manuel De Régulation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2.3 Machine parameters menu

Fault type
d1
M=Maintenance
D=Danger
0 1 2 3 4 5 6 7 8 9
0x
D D D M D D M D M
1x D D M M D D M M M M
2x M M M M D M M M M M
List of faults:
Order
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Configuration
c1
Add. filter
-----
Return air filter
-----
Return air fan
-----
Add. filter: Without, With
Return air filter: Without, With
Return air fan: Without, With
Level 2 access. This screen is used to configure the criticality of the faults managed by the regulating controller
If a fault is shown as "Danger" the unit will be switched off. If the fault is shown as "Maintenance", only an alarm
message will be indicated.
Criticality of faults 1 to 9
Criticality of faults 10 to 19
Criticality of faults 20 to 29
poor exhaust air flow
Exhaust filter clogged
Additional filter clogged
Electric heater safety thermostat
Low intake temperature
High intake temperature
Low ambient or exhaust temperature
High ambient or exhaust temperature
Heat recovery unit frosted
Variable speed rotary recovery
Low ambient or exhaust humidity
High ambient or exhaust humidity
Heat recovery unit fouled
Brine water pump motor
Level 3 access
Description
Intake motor
Exhaust motor
poor intake air flow
Intake filter dirty
Intake filter clogged
Exhaust filter dirty
Additional filter dirty
Damper
Burner
Overheating
Frost protection
Heat pump module
Clock lithium battery
Duct pressure
Humidifier
EN - 22
Significance
Danger
Danger
Danger
Maintenance
Danger
Danger
Maintenance
Danger
Maintenance
Danger
Danger
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance

Publicité

Chapitres

Table des Matières
loading

Table des Matières