5.5.3 Configuration process
The diagram below illustrates the phases of the "configuration process" required for configuring the card correctly:
XML file
No group
addresses
ETS
projects
.pr5 file
OFF-line: linkage of variables
The types of KNX Datapoint available and the respective conversion methods are listed in the table below:
The first step of the configuration is performed OFFline (i.e. disconnected from the network). It consists of defining, within ETS,
the list of products used in the project and of defining the group addresses (i.e. the data which will be exchanged between the
KNX controllers).
The special feature of the KNX controller for air handling units is that the allocation of the group addresses is not performed from
ETS but from the KSet software.
The creation of air handling controllers in the ETS project requires the use of a plug-in, which also enables the xml file generated
with KSet to be imported and uploaded to the air handling unit controller.
KSet software
To allocate the group addresses OFFline, install and open the KSet software.
In the File menu, open the xml file provided.
The Group column has already been completed with the default group addresses. Delete the group addresses opposite the KNX
datapoints which do not apply to the project, and edit the group addresses for the datapoints relevant to the project if the defaults
do not apply.
Do not make any changes to the other columns.
When all the group addresses have been defined, save the xml file (File menu) with another name.
The types of KNX Datapoint available and the respective conversion methods are listed in the table below:
Type
Name
Boolean
(DPT_Switch)
Unsigned 8 bit
(DPT_Value_1_Ucount)
Signed 8 bit
(DPT_Value_1_Count)
Unsigned 16 bits
(DPT_Value_2_Ucount)
Signed 16 bits
(DPT_Value_2_Count)
Floating 16 bits
(DPT_Value_Temp)
It is important to remember itself that the same address of group cannot be assigned to more than Datapoint
kSET:
Enter the group
addresses
ETS
Create the links
between the
various datapoints,
i.e., allocate the
group addresses
Standard ID
1.001
1 bit
5.010
Unsigned 8 bits
6.010
Signed 8 bits
7.001
Unsigned 16 bits
8.001
Signed 16 bits
9.001
Floating 16 bits
ETS
Assign the addresses
for the air handling unit
and configure the other
products
Format
KNX range
Off / On
0 to 255
-128 to +127
0 to 65535
-32768 to +32767
-671088.64 to +670760.96
EN - 58
XML file
complete
XML file
Download the XML
file in the air handling
unit (table with group
addresses)
END
of installation
Range
available in the
controller
Off / On
0 to 255
-128 to +127
0 to 32767
-32768 to +32767
-3276.8 to +3276.7