CIAT AirControl CTA Manuel De Régulation page 115

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Register hex.
Register
no.
decimal no.
0x494
1172
0x495
1173
0x497
1175
0x498
1176
0x499
1177
0x49A
1178
0x49B
1179
0x49C
1180
0x49D
1181
0x49E
1182
0x4A5
1189
0x4A6
1190
0x4AB
1195
0x4AC
1196
0x4B2
1202
0x4B3
1203
0x4B4
1204
0x4B5
1205
0x4B6
1206
0x4B7
1207
0x4B8
1208
0x4B9
1209
0x4CC
1228
0x4CD
1229
0x4D2
1234
0x4D3
1235
0x4D8
1240
0x4D9
1241
0x4DA
1242
0x4DB
1243
0x4DC
1244
0x4DD
1245
0x4DE
1246
0x4DF
1247
0x4E0
1248
0x4E1
1249
0x4E2
1250
0x4E3
1251
0x4E4
1252
0x4E5
1253
0x4E6
1254
0x500
1280
0x501
1281
0x502
1282
Description
Return air fan state
control signal for the rotary heat recovery fixed speed or brine
pump
Burner control output state
Burner stage 1 state
Burner stage 2 state
burner power percentage
Burner command direction of action
Heat recovery unit bypass output value
Heat recovery unit bypass control direction of action
Calculated supply air setpoint value
Supply air fan runtime counters
Option to reset the counters
Return air fan runtime counters
Option to reset the counters
Stage 1 electric heater runtime counters
Option to reset the counters
Stage 2 electric heater runtime counters
Option to reset the counters
Stage 3 electric heater runtime counters
Option to reset the counters
Humidifier runtime counters
Option to reset the counters
Burner runtime counters
Option to reset the counters
operating time counters, rotary heat recovery or brine pump
Option to reset the counters
Adiabatic cooling runtime counter
Option to reset the counters
Software version number
Suffix number
Day
Month
Year
Bios version
Bios suffix
Boot version
Boot suffix
SO number part 1
SO number part 2
Box number part 1
Box number part 2
Unit state
Heating requirement supplied by unit
Cooling requirement supplied by unit
Format
Boolean
Boolean
Boolean
Boolean
Boolean
Integer
Integer
Integer
Integer
Integer
Integer
Boolean
Integer
Boolean
Integer
Boolean
Integer
Boolean
Integer
Boolean
Integer
Boolean
Integer
Boolean
Integer
Boolean
Integer
Boolean
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
EN - 49
Type
Values displayed
Read-only
0 = Off
1 = On
Read-only
Read-only
0 = Off
1 = On
Read-only
0 = Off
1 = On
Read-only
0 = Off
1 = On
Read-only
Read-only
0:None
1:Increase
2:Decrease
Read-only
Read-only
0:None
1:Opening
2:Closed
Read-only
Value x10
Read-only
in hours
Read/Write
1 = Reset
Read-only
in hours
Read/Write
1 = Reset
Read-only
in hours
Read/Write
1 = Reset
Read-only
in hours
Read/Write
1 = Reset
Read-only
in hours
Read/Write
1 = Reset
Read-only
in hours
Read/Write
1 = Reset
Read-only
in hours
Read/Write
1 = Reset
Read-only
in hours
Read/Write
1 = Reset
Read-only
in hours
Read/Write
1 = Reset
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
0: Off
1: On
2: On after power failure
3: Standby
4: Off by a fault
5: Off by CMS
6: Post ventilation
7: Manual mode
Read-only
Read-only
EN

Publicité

Chapitres

Table des Matières
loading

Table des Matières