CIAT AirControl CTA Manuel De Régulation page 118

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type
Index
DGT
--
DGT
--
5.4.3 Analogue variables
Type
Index
ANL
1
ANL
2
ANL
3
ANL
4
ANL
5
ANL
8
9
ANL
ANL
16
ANL
17
ANL
18
ANL
19
ANL
25
ANL
26
ANL
27
ANL
28
ANL
29
ANL
30
ANL
37
ANL
44
ANL
44
ANL
45
ANL
45
ANL
48
ANL
48
ANL
49
ANL
49
NV name
SNVT
nvo_alarm_01_16
83
nvo_alarm_17_32
83
NV name
SNVT
113
nvo_custom_1
nvo_custom_2
113
nvo_custom_3
113
nvo_custom_4
113
nvo_custom_5
113
nvo_custom_8
161
nvo_custom_9
161
nvo_custom_16
105
nvo_custom_17
105
nvo_custom_18
105
nvo_custom_19
105
nvo_sortie_ana_1
9
nvo_sortie_ana_2
9
nvo_sortie_ana_3
9
nvo_sortie_ana_4
9
nvo_sortie_ana_5
9
nvo_sortie_ana_6
9
nvo_etat_unite
9
nvi_T_regul
105
nvo_T_regul
105
nvi_T_souf_B
105
nvo_T_souf_B
105
nvi_D_regul
161
nvo_D_regul
161
nvi_P_regul
113
nvo_P_regul
113
Direction
output
Alarm 1 value:
bit 0
Motor alarm
bit 1
Return air motor alarm
bit 2
Poor supply air flow alarm
bit 3
Supply air filter 1 dirty alarm
bit 4
Supply air filter 1 blocked alarm
bit 5
Poor return air flow alarm
bit 6
Return air filter 2 dirty alarm
bit 7
Return air filter 2 blocked alarm
bit 8
Additional filter 3 dirty alarm
bit 9
Additional filter 3 blocked alarm
bit 10
Damper alarm
bit 11
Burner alarm
bit 12
Overheating alarm
bit 13
Fire alarm
bit 14
Frost protection alarm
Electric heater safety thermostat alarm
bit 15
output
Alarm 2 value:
bit 0
Low supply air temperature alarm
bit 1
High supply air temperature alarm
bit 2
Low ambient or return air temperature alarm
bit 3
High ambient or return air temperature alarm
bit 4
Heat pump unit alarm
bit 5
Frosted heat exchanger alarm
bit 6
Rotary heat exchanger alarm
bit 7
Clock lithium battery alarm
bit 8
Duct pressure alarm
bit 9
Low ambient or return air humidity alarm
bit 10
High ambient or return air humidity alarm
bit 11
Humidifier alarm
bit 12
Heat recovery unit fouled alarm
water recovery pump alarm Brine
bit 13
Direction
output
Supply air filter 1 fouling level
output
Supply air duct pressure
output
Return air filter 2 fouling level
output
Additional filter 3 fouling level
output
Heat recovery unit fouling level
output
Supply air fan flow rate
output
Return air fan flow rate
output
Room or return air temperature
output
Supply air temperature
output
Fresh air temperature
output
Network water temperature
Water coil No.1 capacity
output
output
Water coil No.2 capacity
output
Supply air variable drive
output
Return air variable drive
output
Triac
output
Rotary heat exchanger speed
output
Unit operating state:
Value 0
off
Value 1
opening of damper
Value 2
on
Value 3
switched on after a power failure
Value 4
standby
Value 5
switched off by a fault
Value 6
switched off by CMS
Value 7
post ventilation
input
Regulated temperature setpoint (return or room)
output
Regulated temperature setpoint return (return or room)
input
Supply air only temperature setpoint
output
Supply air only temperature setpoint return
input
Supply air fan flow rate setpoint
output
Supply air fan flow rate setpoint return
input
Supply air duct pressure setpoint
output
Supply air duct pressure setpoint return
EN - 52
Description
Description

Publicité

Chapitres

Table des Matières
loading

Table des Matières