CIAT AirControl CTA Manuel De Régulation page 123

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Description
Alarm 2 value:
Bit 0 = Low supply air temperature
alarm
Bit 1 = High supply air temperature
alarm
Bit 2 = Low ambient or return air
temperature alarm
Bit 3 = High ambient or return air
temperature alarm
Bit 4 = Heat pump unit alarm
Bit 5 = Heat recovery unit frosted
alarm
Bit 6 = Rotary heat exchanger alarm
Bit 7 = Timer lithium battery alarm
Bit 8 = Duct pressure alarm
Bit 9 = Low ambient or return air
humidity alarm
Bit 10 = High ambient or return air
humidity alarm
Bit 11 = Humidifier alarm
Bit 12 = Heat recovery unit alarm
Bit 13 = water pump alarm Brine
recovery
Heating requirement supplied by unit
Cooling requirement supplied by unit
Unit On/Off command via CMS
Unit On/Off control return via CMS
Reset of alarms not present command
Reset of alarms not present command
return
Electric heater load shedding
Electric heater load shedding return
Temperature-dependent machine
actuation in Eco / Comfort mode
Temperature-dependent machine
actuation return in Eco / Comfort
mode
Flow rate-dependent machine
actuation in Eco / Comfort mode
Flow rate-dependent machine
actuation return in Eco / Comfort
mode
Pressure-dependent machine
actuation in Eco / Comfort mode
Pressure-dependent machine
actuation return in Eco / Comfort
mode
Choice of heating coil
Choice of heating coil return
Damper control (frost protection or
insulation)
Electric heater stage 1 control
Electric heater stage 2 control
Electric heater stage 3 control
Adiabatic cooling control
Supply air fan control
Return air fan control
Control of rotary heat recovery or
fixed speed pump brine recovery
Burner order command
Burner stage 1 command
Burner stage 2 command
"Danger" fault summary
"Maintenance" fault summary
Data
Data type
Alarme2
DPT_Value_2_
Ucount
Chaud
DPT_Value_2_
Ucount
Froid
DPT_Value_2_
Ucount
OnoffGTC
DPT_Switch
OnoffGTC
DPT_Switch
ResetAlarmes
DPT_Switch
ResetAlarmes
DPT_Switch
Delestage
DPT_Switch
Delestage
DPT_Switch
ConfortEcoTemp
DPT_Switch
ConfortEcoTemp
DPT_Switch
ConfortEcoDebit
DPT_Switch
ConfortEcoDebit
DPT_Switch
ConfortEcoPression
DPT_Switch
ConfortEcoPression
DPT_Switch
ChoixBatterieChaud
DPT_Switch
ChoixBatterieChaud
DPT_Switch
Registre
DPT_Switch
BattElec1
DPT_Switch
BattElec2
DPT_Switch
BattElec3
DPT_Switch
RafraichissementAdiab
DPT_Switch
VentilateurSoufflage
DPT_Switch
VentilateurReprise
DPT_Switch
RoueFixe
DPT_Switch
OrdreBruleur
DPT_Switch
BruleurAllure21
DPT_Switch
BruleurAllure2
DPT_Switch
DefautDanger
DPT_Switch
DefautMaintenance
DPT_Switch
EN - 57
Code type
IN/OUT
Index
7.001
OUT
29
7.001
OUT
1281
7.001
OUT
1282
1.001
IN
280
1.001
OUT
280
1.001
IN
281
1.001
OUT
281
1.001
IN
282
1.001
OUT
282
1.001
IN
283
1.001
OUT
283
1.001
IN
284
1.001
OUT
284
1.001
IN
285
1.001
OUT
285
1.001
IN
290
1.001
OUT
290
1.001
OUT
1155
1.001
OUT
1156
1.001
OUT
1157
1.001
OUT
1158
1.001
OUT
1167
1.001
OUT
1171
1.001
OUT
1172
1.001
OUT
1173
1.001
OUT
1175
1.001
OUT
1176
1.001
OUT
1177
1.001
OUT
1300
1.001
OUT
1301
TYPE
Coef
REG
1
EN
REG
1
REG
1
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL
COIL

Publicité