Setpoint Menu - CIAT AirControl CTA Manuel De Régulation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

To switch to another menu, press the  or  buttons to scroll through the available menus. The selected menu is opposite the
arrow and on a black background. To confirm your choice, simply press enter or ↵
The available menus are as follows:
- 1. Setpoints
- 2. Machine status
- 4. Machine parameters
- 5. Settings parameters
- 6. Reading parameters
- 7. Fault memory
- 8. Test mode
- 9. Timer prog.
- 11. Communication
- 12. Alarms
- 14. Access levels
- 16. Versions

2.2 Setpoint menu

Comfort
w0
Fan flow rate
Supply air
010000m3/h
Return air
010000m3/h
Eco
Supply air
005000m3/h
Return air
005000m3/h
Comfort
w1
Duct pressure
200Pa
Eco 100Pa
Comfort
w2
Return air
20.0°C
Eco 15.0°C
Supply air
a
Upper limit
26.0°C
Lower limit
16.0°C
w3
Air quality
0800ppm
Maximum flow rate
010000m3/h
"Prg" button
14. Access level
16.Versions
1.Setpoints
2.Machine state
4.Machine parameters
Indication of the operating mode
Supply air fan Comfort flow rate control setpoint
Return air fan Comfort flow rate control setpoint
Supply air fan Eco flow rate control setpoint
Return air fan Eco flow rate control setpoint
Indication of the operating mode
Comfort pressure control setpoint for the supply air duct
Eco pressure control setpoint for the supply air duct
Indication of the operating mode for T° control in "Precision" mode Level 1 Access
Comfort (Return or Ambient air) temperature control setpoint monitored (0 to 50.0°C)
Eco (Return or Ambient) temperature control setpoint monitored (0 to 50.0°C)
Upper limit for calculated Supply air T° setpoint
Lower limit for calculated Supply air T° setpoint
Level 2 access
Air quality regulation setpoint
Maximum flow rate value of supply air fan for air quality control
Menu
Level 2 access
Level 2 access
EN - 19
EN

Publicité

Chapitres

Table des Matières
loading

Table des Matières