Specifications

9.
INPUT
Voltage Range (VAC)
Frequency (Hz)
Number of phases
Input Power factor
THD
OUTPUT
Voltage Range (VAC)
Voltage adjustment
Voltage regulation
Capacity
Power Factor
Output wave form
Frequency stability
Frequency regulation
Transfer time
Crest factor
Efficiency
Nominal autonomy
Cold start
BATTERY
Capacity
Quantity
Voltage (V)
Recharge time
DISPLAY
Status on LCD and LED
Data specified on LCD
Self-diagnostics
PROTECTION
Short circuit
Over heating
Low battery
EPO
Battery
ALARMS
Acoustics & display
PHYSICALS CHARACTERISTICS
Mechanicals dimensions (H x W x D) mm
Net weight + battery weight
Input connectors
Output connectors
ENVIRONMENT
Operating temp, range
Warning temperature
Altitude
Humidity
Noise
INTERFACE COMPUTER
Type
Slots
compatible systems
COMPLIANCE
Security
Standard EMC
Marking
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
53
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 06 11 AA 68 203 03
E6 LCD 1000 RT
115 V : 60/70/80-144
115 V :100/110/115/120/127
1000 VA / 800 W
Pure sine wave, THD <3% (from 0 up to 100% in load)
+/-3Hz or +/-1Hz (program by software)
>85%
> 5 min
12 V / 7 Ah
3
36
Normal, Battery, Bypass, Prog socket 1, Prog socket 2, Auto test, Low battery, Default Battery,
Default connection, Default, Overload, load level and battery level
Input voltage, Input frequency, Output voltage, Frequency voltage, charge level,
Voltage battery, internal Temperature
Mains mode : Bypass Transfer - Battery Mode : Automatic shutdown
Electronic system of management of battery discharge
Mains default, Low battery, Overload, Environment default
88 x 440 x 405 (2U)
15,1 kg
115 V : NEMA / 230 V : IEC
115 V : 6* NEMA
230 V : 6* IEC
Battery design for use at 25°C. A higher ambient temperature will decrease its life span
0-2000 m up to 40°C / 3000 m up to 35°C
Windows 95/98/NT/2000/XP/Vista, Novell Netware, Linux etc
EN 62040-2, EN61000-3-2, EN61000-3-3, FCC Class A
E6 LCD 2000 RT
/
230 V : 120/140/160-288
50 / 60 Hz ± 5 Hz (Auto detection)
Single phase + ground
> 0,99 (full load)
-
/
230 V :200/208/220/230/240
-
< ± 1% up to low battery alarm
2000 VA / 1600 W
0,8
± 1% (battery mode)
0 ms
3:1
> 5 min
Yes
12 V / 7 Ah
6
3 hours at 90%
In mains mode and by software
Off mode immediately
Alarm and automatic stop
Switch Off Stop immediately
88 x 440 x 650 (2U)
27,9 kg
115 V : NEMA / 230 V : IEC
115 V : 2* 5-15R+ 2* 5-20R
230 V : 6* IEC
0 - 40°C
90% max without condensation
< 50dB (at 1 m)
Standard RS 232 or USB
relay card, SNMP/Web card
EN62040-1-1, IEC 60950-1
CE, UL, cUL, FCC
E6 LCD 3000 RT
3000 VA / 2400 W
>88%
> 4 min
12 V / 9 Ah
6
72
29,7 kg
115 V : NEMA / 230 V : IEC
115 V : 4* 5-15R+1* L5-30R
230 V : 4* IEC 10A +1*IEC 16A

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

E6 lcd 2000 rtE6 lcd 3000 rt

Table des Matières