Input Conductors; Input Connection Procedure - ESAB EPP-400 Manuel D'instructions

Source d'alimentation pour plasma
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 174
sectIon 3

3.4.2 Input conductors

Customer supplied
May consist either of heavy rubber covered copper conductors (three power and one ground) or run
in solid or flexible conduit.
Sized according to the chart.
notIce

3.4.3 Input connection procedure

3
1 = primary terminals
2 = chassis ground
3 = power Input cable access opening (rear panel)
Input conductors must be terminated with ring terminals.
Input conductors must be terminated with ring terminals sized for
12.7 mm (0.50") hardware before being attached to the epp-400.
1
2
1. Remove left side panel of the EPP-400
2. Thread cables through the access opening in the rear panel.
3. Secure cables with a strain relief or conduit coupling (not sup-
plied) at the access opening.
4. Connect the ground lead to the stud on the chassis base.
5. Connect the power lead ring terminals to the primary termi-
nals with supplied bolts, washers and nuts.
6. Connect the input conductors to the line (wall) disconnect.