SV2 Series Replacement Solenoids
WARNING
Electric Shock Hazard
Can cause serious personal injury or death.
• Disconnect power supply before beginning
installation.
• More than one disconnection can be involved.
Replacement Solenoid Selection
The SV2 Series valves individual solenoid coils may be replaced in the field, should the necessity occur, without replacing the
entire valve.
Replacement solenoid part numbers are identified by 'COIL', followed by the valve body size designation and applicable voltage.
Each replacement solenoid will work on all valve intelligence levels and models as indicated in Table 1.
Replacement solenoids are sold and shipped one (1) per box.
Valve Intelligence
Valve Models
Level
All:
All:
V2F
V2A
V2V
V2P
1. Valve Intelligence Levels are defined as:
5 = BASIC. No Modbus or Pressure Module compatibility.
6 = STANDARD. Includes Modbus, Pressure Module compatible, external VPS using Pressure Module
7 = ENHANCED. Includes Modbus, Pressure Module compatible, external VPS using Pressure Module, metering (EU future release)
8 = FULL. Includes Modbus, Pressure Module compatible, internal VPS using Pressure Module, metering (EU future release)
9 = ELITE. Includes Modbus, Pressure Module compatible, internal VPS using Pressure Module, metering, leak detection sequence (North America future release)
Removal of Original Solenoid
1. Ensure that:
a.
The line voltage has been removed from the valve.
b. The gas supply is turned off and that the manual safety shut-off valve(s) are closed.
c. The valve is stabilized and will not tip over or fall.
2. Remove the valve front electrical enclosure retaining screws with the appropriate
tool to access the wiring terminals.
3. Remove the valve rear enclosure retaining screws with the appropriate tool to
access the solenoids.
Enclosure
Rating
1
All:
5
NEMA 4 /
6
IP66
7
NEMA 1 /
8
IP20
9
Table 1. Available Replacement Solenoids.
WARNING
Explosion Hazard and Electrical Shock Hazard.
Can cause explosion, serious injury or death.
• Disconnect the power supply making wiring
connection to prevent electrical shock and
equipment damage.s
• More than one power supply disconnect can be
involved.
Valve Sizes
A / B
¾ and 1 inch
(DN20 and DN25)
0.5-1.0 MMBTu
(150-300 kW)
at 4 in w.c. pressure drop
C / D
1 ½ and 2 inch
(DN40 and DN50)
2.6-4.6 MMBTu
(750-1348 kW)
at 4 in w.c. pressure drop
PORT M (MID
PRESSURE)
MODULE
2
LOCATING
HOLES
PORT O
(OUTLET
PRESSURE)
Voltage / Phase
24VAC
COILAB024V-000
50/50Hz
100-120VAC
COILAB120V-000
50/50Hz
200-240VAC
COILAB240V-000
50/50Hz
24VAC
COILCD024V-000
50/50Hz
100-120VAC
COILCD120V-000
50/50Hz
200-240VAC
COILCD240V-000
50/50Hz
LGP
HGP
Open
Open
Fault
Closed
Self Test
Reset
Closed
PORT I
PORT I (INLET
(INLET
PRESSURE)
PRESSURE)
MODULE
LOCATING
MODULE
HOLES
LOCATING
HOLES
PORT M (MID
PRESSURE)
PORT M (MID
PORT R
PRESSURE)
PORT R
(REGULATOR
(REGULATOR
SERVO)
PORT R
SERVO)
(REGULATOR
SERVO)
Solenoid
PORT M (MID
PRESSURE)
MODULE
32-00038EFSP—01
LOCATING
HOLES
PORT O
(OUTLET
PRESSURE)
PORT R
(REGULATOR
SERVO)
M35486

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Coilabv serieCoilcdv serie

Table des Matières