Technical Specifications; Operating Conditions; Generating Set Identification - Kohler SDMO TECHNIC 6500 A AVR C5 Manuel D'utilisation Et D'entretien

Masquer les pouces Voir aussi pour SDMO TECHNIC 6500 A AVR C5:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1

8 Technical specifications

8.1

Operating conditions

The stated outputs of the units are obtained under the reference conditions outlined in ISO 8528-1(2005):
Total barometric pressure: 100 kPa - Ambient air temperature: 25°C (298 K) - Relative humidity: 30%.
The unit's output is reduced by approximately 4% for every additional 10°C and/or approximately 1% for every additional 100m in
altitude. Units can only operate while stationary.
8.2
Capacity of the generating set
Before connecting and operating the unit, calculate the electrical power required by the units to be used (in watts)*. To ensure
optimal operation, the total wattage of all equipment used at the same time must be:
-
greater than 60% of the rated load for the unit (risk of insufficient load);
-
less than the rated load for the unit during continuous operation (risk of overload).
If the unit is run under or over its rated load frequently or for long periods of time, it can start to wear very quickly. Damage caused
in this way will not be covered by the warranty.
*
This load is usually indicated in the technical specifications or on the manufacturer's plate for the equipment. Some equipment requires a higher
load when starting. This minimum required power must not exceed the unit's maximum power
8.3

Generating set identification

The identification plate for the unit (example shown below) is affixed inside one of the skirts or on the chassis.
(C)
(B)
Serial numbers will be required when requesting troubleshooting advice or spare parts. For your records, please enter the unit and
engine serial numbers below.
Unit serial number:
....../.............. - ........................... - .........
8.4
Specifications
Model
Maximum power
Rated output
Acoustic pressure at 1 m
Acoustic measurement uncertainty
Engine type
Maintenance kit
Fuel tank capacity
Recommended fuel
Recommended oil
Oil sump capacity
Oil cut-out*
Direct current
Alternating current
Circuit breaker(s)**
Socket type
Spark plug type
Battery
Dimensions l x w x h
Weight (without fuel)
o: standard
*Oil cut-out: If there is no oil in the engine sump or if the oil pressure is low, the oil cut-out mechanism automatically stops the engine to prevent any
damage. If this occurs, check the engine oil level and top it up if necessary before looking for any other cause of the problem.
**Circuit breaker: The generating set's electrical circuit is protected by one or more magnetothermal, differential or thermal cut-out switches. In the
event of an overload and/or short circuit, the supply of electrical energy may be cut. If necessary, replace the circuit breakers in the generating set
with circuit breakers with identical nominal ratings and specifications.
8.5
Authorised fuel
Using fuel which does not comply with the following specifications exposes the equipment to irreversible damage not covered under
warranty:
-
Cleanliness and quality: ensure that the petrol used does not contain water and that it is fresh and clean (not out of date or
contaminated). For the
-
Octane rating: minimum octane rating of 87 (R+M)/2 or minimum octane rating of 90 (RON = Research Octane Number)
-
Blends: the use of unleaded petrol containing up to 10% ethyl alcohol is authorised (France: SP95-E10). It is not permitted
to use unleaded petrol containing less than 90% petrol, e.g. E15, E20 or E85. Blends of methyl tert-butyl ether (MTBE) and
unleaded petrol are approved (up to a maximum of 15% MTBE by volume).
However, it is strongly recommended that the same type of fuel is used throughout the complete service life of the unit. If the unit is
used infrequently (less than once a month), use new fuel with each use or add a stabilizing additive to the fuel tank.
(G)
(D)
(E)
(H)
(F)
(I)
(A)
(M)
........................................
TECHNIC 6500 A AVR C5
2X2P+T-230V 10/16/32A
.
(A):
Model
(B):
CE/EAC marking
(C):
Guaranteed acoustic
(J)
power level
(D):
Maximum power
(K)
(E):
Nominal power
(L)
(F):
Power factor
Engine manufacturer:(e.g.
Kohler)
6300 W
5200 W
83 dB(A)
0,40 dB(A)
CH440E_C5
RKS2
18 L
Unleaded petrol
10W30
1,29 L
O
X
230V - 22,6A
O
330830012
O
81 x 55,5 x 59 cm
101 kg
x: not available
21/216
(G):
Ground
(H):
Current amperage
(I):
Current frequency
(J):
Current voltage
(K):
Protection rating
(L):
Reference standard
(M):
Serial number
Engine serial number: (e.g Kohler (SERIAL
NO. 4001200908))
......................................................
TECHNIC 7500 TA AVR C5
6500 W
5200 W
83 dB(A)
0,40 dB(A)
CH440E_C5
RKS2
18 L
Unleaded petrol
10W30
1,29 L
O
X
400V - 7,5A
O
1P+T -230V 10/16A + 1P+T 400V 16A
330830012
O
81 x 55,5 x 59 cm
102kg

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sdmo technic 7500 ta avr c5

Table des Matières