Kohler SDMO TECHNIC 6500 A AVR C5 Manuel D'utilisation Et D'entretien page 24

Masquer les pouces Voir aussi pour SDMO TECHNIC 6500 A AVR C5:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
7.2
APM202 faults and alarms
Pictograms
Colour of the LED
Red
Flashing red
Red
Red
Red
Red
Flashing green
7.3
Diagnostics for minor faults
The generating set...
Does not start
Stops
Does not function normally
(noise, smoke, etc.)
Does not supply electrical
current
7.4
Generator Smart Care
If the unit has been equipped with the "GS101-Generator Smart Care" option (A26),
it is necessary to change the batteries in the Bluetooth GSC101 box when the
warning is displayed in the Generator Smart Care application (approximately every
two years).
1.
Use a small crosshead screwdriver to open the cover of the box,
2.
Remove the used batteries and take them to a waste collection point so
that they can be recycled,
3.
Fit two new AAA batteries, observing the polarity (+/-),
4.
Close the unit cover and carefully tighten the screws.
Type of fault
Shutdown: generating set rotation
Overspeed
Shutdown: insufficient generating
Speed too low
3 or 6 unsuccessful attempts
Fail to start
(depending on the engine type) in
Oil pressure or low
Shutdown: incorrect oil pressure
oil level
Battery or charging
alternator
charge output or weak battery
Engine temperature
Glow plug
preheating or choke
Check that:
The checks before starting have been
performed.
YES
The battery is correctly connected and
charged.
YES
The fuel tap is open.
YES
The spark plug(s) is/are in good
condition and correctly connected.
YES
The devices to be used have not been
connected prior to starting.
YES
The APM202 fuses are not faulty (the
indicator lights come on).
YES
The oil level is correct.
YES
The fuel level is correct.
YES
Maintenance has been correctly
performed on the generating set
components.
YES
Have the generating set checked by
one of our agents.
Tripped circuit breaker(s).
YES
The connected devices and their power
cords are not faulty.
YES
Have the generating set checked by
one of our agents.
Issue
speed excessive
set rotation speed
succession
or low oil level
Problem with the alternator
Shutdown: abnormal engine
temperature
No issue: choke or plug
preheating sequence
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
20/216
Possible solution
Contact one of our agents.
Contact one of our agents.
Check that the generating set has
been started according to the
recommendations in this manual.
Allow the generating set to cool
down, top up and check the oil level.
Contact one of our agents.
Allow the generating set to cool down
and check the air filter and vents on
the enclosure.
-
Solutions to be applied:
Perform the checks.
Install the battery; replace it with a new
battery if necessary.
Open the fuel tap.
Check the spark plug(s).
Disconnect the devices then try to restart
the generating set
Have the generating set checked by one of
our agents.
Top up with oil.
Fill up with fuel.
Perform maintenance on the generating
set in accordance with the
recommendations
Check the capacity of the generating set
and press the circuit breakers.
Try with another device and another power
cord.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sdmo technic 7500 ta avr c5

Table des Matières