The speed of response adjustment allows the user to collectively set a number of operating
parameters.
measurement response:
agitator discrimination:
filter:
fail-safe timer:
SP
measurement response
1*
1 m/min (3.3 ft/min)
2
5 m/min (16.4 ft/min)
3
immediate
4
0.03 m/min (0.1 ft/min)
* = factory setting
• To change the speed of response, obtain the `SP' display.
• Scroll forward through the options (1-2-3) by pressing the "20" key. Scroll backward through the
options (3-2-1) by pressing the "4" key.
• When the desired option is displayed, stop pressing the key. The display will automatically return
to the Run mode (6 sec).
Fail-Safe
In the event a loss of echo or fault condition exceeds the `Waiting' period (see Speed of Response
above or Fail-safe Timer on page 11), the ` ? ' icon appears and one of the following fail-safe defaults
is immediately effected.
FLS
1
2
3*
p = proportional span
• To change the fail-safe default obtain the `FLS' display.
• Scroll forward through the options (1-2-3) by pressing the "20" key. Scroll backward through the
options (3-2-1) by pressing the "4" key.
Page 10
is the limit to which The Probe will be able to keep up with rates of change.
If The Probe measurement cannot keep up with the rate of level change, set the
adjustment from `1' to `2'. If The Probe still cannot keep up with the rate of level
change, set the adjustment option to `3'. Avoid choosing an option that is too fast for
your application.
discriminates between agitator blades in motion, and the material (target) surface.
discriminates between false echoes from acoustical and electrical noise and the
material (target) surface.
establishes the `Waiting' period from the time a loss of echo or operating fault
condition starts until the fail-safe default is effected. Adjusting the speed of
response will set the fail-safe timer to the default values in the chart. If a different
response is required, adjust the 'FSt' option (see page 11).
agitator discrimination
speed of response
3 sec
current option i.e. 1 m/min
press "20" for option 2 i.e. 5 m/min
option 2 selected
6 sec
default
full
empty
hold
i = inversely proportional span
The Probe – INSTRUCTION MANUAL
filter
on
on
off
on
p
i
mA
mA
22
4
4
22
hold
hold
* = factory default
fail-safe timer
on
10 min
on
3 min
off
3 min
on
10 min
reading
hold
hold
hold
7ML19985GC62