Dri-Eaz DriTec 4000i Manuel Du Propriétaire page 9

Masquer les pouces Voir aussi pour DriTec 4000i:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

TROUBLESHOOTING
F A U L T
Separate circuit in-
dicator light does
not illuminate
Circuit breaker trips
after a few minutes
of operation.
Unit does not oper-
ate
Unit operating, but
room not dry
Unit removes too
little water
If the problem you are experiencing is not listed here, call your local distributor or contact
our Service Department toll-free at 800-932-3030 for further assistance.
SPECIFICATIONS
Power
Amps (max.)
Amps (at 80°F/60%RH)
Process air
Reactivation air
Water removal
(at 80°F/60%RH)
Weight
Dimensions (H × W × D)
Air filter
Safety
WARNING: This product may expose you to
chemicals, including lead and phthalates, known
to the State of California to cause cancer, birth defects,
or other reproductive harm. For more information, go to
P65Warnings.ca.gov
49-109H F533
C A U S E
Unit not plugged into two sepa-
rate circuits.
Incorrect wiring in the building.
Reactivation outlet not ducted.
Ducting is kinked or blocked.
Excessively long ducting.
Unit not switched on.
No power to machine.
Not enough time to dry.
Poor air movement in room.
Excessive moist air infiltration.
Room air is dry.
Inlet air temperature is too warm.
Inlet air temperature is too damp.
Filter is clogged.
115V / 60 Hz
24
Circuit 1: 10.7
Circuit 2: 10.8
395 CFM
65 CFM
118 pints/day | 55.8 L per/day
95 lbs. | 43.1 kg
33.13 × 21.14 × 20.25 in.
(With handle upright = 42. 250 in.)
84.15 × 53.7 × 51.4 cm
(With handle upright = 107.3 cm.)
F590 (24 pk)
ETL listed to CSA dehumidifier
standards
S O L U T I O N
Plug unit into two separate circuits rated for at least 15
amps each.
Locate a second 15 amp circuit in the structure.
The Reactivation Out must always be ducted out of the
area being ducted.
Straighten all ducting as much as possible; remove any
blockages.
React ducting length should not exceed 20 ft. (6 m).
Switch unit on.
Check power cord connections at wall outlet and in top
compartment of unit. Check supply circuit breakers.
Allow more time for drying.
Increase evaporation with air movers.
Seal off area to reduce infiltration.
Confirm humidity level with hygrometer.
Decrease temperature of intake air.
Decrease humidity of intake air.
Check filter. Clean or replace as necessary.
PARTS INCLUDED
 Reactivation Out duct ring adapter
 Reactivation Out heat-resistant ducting, 20 ft. × 6 in.
 6 in. duct clamp
 Air inlet duct ring adapter (optional, installation requi-
red)
 Process air outlet layflat duct adaptor kit (optional,
installation required)
 Two power cords, 25 ft. each
OPTIONAL
Layflat ducting for process air outlet (F536)
ADDITIONAL PRODUCT INFORMATION and current
documentation is available at www.LegendBrandsResto-
ration.com.
FOR PARTS AND SERVICE CALL YOUR LOCAL DIS-
TRIBUTOR or Dri-Eaz at 800-932-3030. www.Legend-
BrandsRestoration.com
Visit warranty.LegendBrandsRestoration.com and regis-
ter your purchase to ensure you receive any important
product releases.
9
Dri-Eaz Products, Inc.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

F533

Table des Matières